General technical specifications |
Degree of protection | IP20 acc. to IEC 529 |
Ambient temperature | |
| |
| -20 ... +60 °C |
| -20 ... +50 °C |
- Transportation and storage
| -40 ... +70 °C |
| 25 ... 55 °C |
Insulation | |
| 500 V AC test voltage |
- 115/230 V AC circuits to ground
| 1500 V AC test voltage |
- 115/230 V AC circuits to 115/230 V AC circuits
| 1500 V AC test voltage |
- 230 V AC circuits to 5/24 V DC circuits
| 1500 V AC test voltage |
- 115 V AC circuits to 5/24 V DC circuits
| 1500 V AC test voltage |
Electromagnetic compatibility | Requirements of the EMC directive |
- Noise immunity acc. to
EN 50082-2
| Test acc. to: IEC 801-2, IEC 801-3, IEC 801-4, EN 50141, EN 50204, IEC 801-5, VDE 0160 |
- Emitted interference acc. to EN 50081-1 and
EN 50081-2
| Test according to EN 55011, Class A, Group 1 |
Mechanical strength | |
- Vibrations, test acc. to / tested with
| IEC 68, Part 2-6: 10 ... 57 Hz; constant amplitude 0.3 mm; 58 ... 150 Hz; constant acceleration 1 g (mounted on DIN rail) or 2 g (mounted in switchboard); mode of vibration: frequency sweeps with a sweep rate of 1 octave/minute; duration of vibration: 10 frequency sweeps per axis in each direction of the three mutually perpendicular axes |
- Shocks, test acc. to / tested with