Mains voltage | | 380 V to 480 V 3 AC | 500 V to 600 V 3 AC |
Current (at 40 °C/50 °C) | For frame size A (0.37 to 1.5 kW) | 4.5 A/4.1 A | - |
For frame size B (2.2 to 4 kW) | 11.2 A/10.2 A | - |
For frame size C (0.75 to 4 kW) | - | 9.0 A/6.1 A |
For frame size C (5.5 to 11 kW) | 32.6 A/26 A | 22.4 A/17 A |
For frame size D (15 kW) | 38.8 A/32 A | 27.5 A/22 A |
For frame size D (18.5 kW) | 45.9 A/38 A | 32.6 A/27 A |
For frame size D (22 kW) | 63.2 A/45 A | 41.8 A/32 A |
For frame size E (30 kW) | 76.5 A/62 A | 53 A/41 A |
For frame size E (37 kW) | 112.2 A/90 A | 63.2 A/52 A |
For frame size F (45 kW) | 112.2 A/90 A | 78.5 A/62 A |
For frame size F (55 kW) | 147.9 A/110 A | 101 A/77 A |
For frame size F (75 kW) | 181.6 A/145 A | 127.5 A/99 A |
Current (at 40 °C/55 °C) | For frame size FX (90 kW and 110 kW) | 225 A/191 A | - |
For frame size GX (132 kW) | 276 A/235 A | - |
For frame size GX (160 kW) | 333 A/283 A | - |
For frame size GX (200 kW) | 408 A/347 A | - |
Limiting of motor overvoltage | ? 1078 V |
dV/dt limiting | ? 500 V/?s |
Pulse frequency | 4 kHz |
Max. motor frequency | 150 Hz |
Max. permissible motor cable lengths | For frame sizes A to F | shielded | 200 m |
unshielded | 300 m |
For frame sizes FX and GX | shielded | 300 m |
unshielded | 450 m |
Insulation strength | Overvoltage category III to VDE 0110 |
Electromagnetic compatibility | For frame sizes A to F | Up to 200 m motor cable length with emissions to Class A according to EN 55 011 in conjunction with filtered inverters and unshielded cables |
For frame sizes FX and GX | Up to 150 m motor cable length with emissions to Class A according to EN 55 011 in conjunction with filtered inverters and unshielded cables |
Conformity | CE according to the low-voltage directive 73/23/EEC |
Approvals | cUL E 219022 |
Strain resistance | EN 60 068-2-31 |
Humidity | 95 % humidity, non-condensing |
Degree of protection | For frame sizes A to C | IP20 (to EN 60 529) |
For frame sizes D to F | IP00/IP20 (to EN 60 529 with terminal covers) |
For frame sizes FX and GX | IP00 |
Insulation class | H (180 °C) |
Temperature range | For frame sizes A to F | Operation | -10 °C to +40 °C (+14 °F to +104 °F) | 100 % Pn |
to +50 °C (to +122 °F) | 80 % Pn |
Storage | -25 °C to +70 °C (-13 °F to +158 °F) | |
For frame sizes FX and GX | Operation | -10 °C to +40 °C (+14 °F to +104 °F) | 100 % Pn |
to +55 °C (to +131 °F) | 85 % Pn |
Storage | -40 °C to +70 °C (-40 °F to +158 °F) | |
Installation altitude | For frame sizes A to C | Up to 2000 m | 100 % Pn |
2000 to 4000 m | 62.5 % Pn |
For frame sizes D to F | Up to 1000 m | 100 % Pn |
1000 to 4000 m | 12.5 % derating for each 1000 m |
For frame sizes FX and GX | Up to 2000 m | 100 % Pn |
2000 to 4000 m | 7.5 % derating for each 1000 m |
Mounting position | For frame sizes A to C | Footprint or suspended |
For frame sizes D to F, FX and GX | Upright |
Ventilation clearances | For frame sizes A to C | Top | 100 mm |
Bottom | 100 mm |
Side | 100 mm |
For frame sizes D to F, FX and GX | Top | 100 mm |
Side | 100 mm |
Connection system | Input, litz wire or terminal | 1U1, 1V1, 1W1 |
Output, terminals | 1U2, 1V2, 1W2 |
Torque for conductor connections | | Terminal cross-section | Torque |
For frame sizes A to C | - | 1.5 Nm to 1.8 Nm |
For frame sizes D to F | 16 mm2 | 2.0 Nm to 4.0 Nm |
35 mm2 | 2.5 Nm to 5.0 Nm |
50 mm2 | 3.0 Nm to 6.0 Nm |
95 mm2 | 6.0 Nm to 12.0 Nm |
150 mm2 | 10.0 Nm to 20.0 Nm |
For frame sizes FX and GX | - | 14.0 Nm to 31.0 Nm |
Weight, approx. | For frame size A | 7 kg |
For frame size B | 11 kg |
For frame size C | 8.5 kg to 29 kg |
For frame size D | 21 kg to 42 kg |
For frame size E | 49.5 kg to 67 kg |
For frame size F | 67 kg to 126 kg |
For frame size FX | 135 kg |
For frame size GX | 138 kg to 208 kg |