Mains voltage | 380 V to 480 V 3 AC |
Current (at 40 °C/50 °C) | For frame size C (7.5 to 15 kW) | 32.6 A/26 A |
For frame size D (18.5 kW) | 38.8 A/32 A |
For frame size D (22 kW) | 45.9 A/38 A |
For frame size D (30 kW) | 63.2 A/45 A |
For frame size E (37 kW) | 76.5 A/62 A |
For frame size E (45 kW) | 112.2 A/90 A |
For frame size F (55 kW) | 112.2 A/90 A |
For frame size F (75 kW) | 147.9 A/110 A |
For frame size F (90 kW) | 181.6 A/145 A |
Current (at 40 °C/55 °C) | For frame size FX (110 kW and 132 kW) | 225 A/191 A |
For frame size GX (160 kW) | 276 A/235 A |
For frame size GX (200 kW) | 333 A/283 A |
For frame size GX (250 kW) | 408 A/347 A |
Limiting of motor overvoltage | ? 1078 V |
dV/dt limiting | ? 500 V/?s |
Pulse frequency | 4 kHz |
Max. motor frequency | 150 Hz |
Max. permissible motor cable lengths | For frame sizes C to F | shielded | 200 m |
unshielded | 300 m |
For frame sizes FX and GX | shielded | 300 m |
unshielded | 450 m |
Insulation strength | Overvoltage category III to VDE 0110 |
Electromagnetic compatibility | For frame sizes C to F | Up to 200 m motor cable length with emissions to Class A according to EN 55 011 in conjunction with filtered inverters and unshielded cables |
For frame sizes FX and GX | Up to 150 m motor cable length with emissions to Class A according to EN 55 011 in conjunction with filtered inverters and unshielded cables |
Conformity | CE according to the low-voltage directive 73/23/EEC |
Approvals | cUL E 219022 |
Strain resistance | EN 60 068-2-31 |
Humidity | 95 % humidity, non-condensing |
Degree of protection | For frame size C | IP20 (to EN 60 529) |
For frame sizes D to F | IP00/IP20 (to EN 60 529 with terminal covers) |
For frame sizes FX and GX | IP00 |
Insulation class | H (180 °C) |
Temperature range | For frame sizes C to F | Operation | -10 °C to +40 °C (+14 °F to +104 °F) | 100 % Pn |
to +50 °C (to +122 °F) | 80 % Pn |
Storage | -25 °C to +70 °C (-13 °F to +158 °F) | |
For frame sizes FX and GX | Operation | -10 °C to +40 °C (+14 °F to +104 °F) | 100 % Pn |
to +55 °C (to +131 °F) | 85 % Pn |
Storage | -40 °C to +70 °C (-40 °F to +158 °F) | |
Installation altitude | For frame size C | Up to 2000 m | 100 % Pn |
2000 to 4000 m | 62.5 % Pn |
For frame sizes D to F | Up to 1000 m | 100 % Pn |
1000 to 4000 m | 12.5 % derating for each 1000 m |
For frame sizes FX and GX | Up to 2000 m | 100 % Pn |
2000 to 4000 m | 7.5 % derating for each 1000 m |
Mounting position | For frame size C | Footprint or suspended |
For frame sizes D to F, FX and GX | Upright |
Free space | For frame size C | Top | 100 mm |
Bottom | 100 mm |
Side | 100 mm |
For frame sizes D to F, FX and GX | Top | 100 mm |
Side | 100 mm |
Connection system | Input, litz wire or terminal | 1U1, 1V1, 1W1 |
Output, terminals | 1U2, 1V2, 1W2 |
Torque for conductor connections | | Terminal cross-section | Torque |
For frame size C | - | 1.5 Nm to 1.8 Nm |
For frame sizes D to F | 16 mm2 | 2.0 Nm to 4.0 Nm |
35 mm2 | 2.5 Nm to 5.0 Nm |
50 mm2 | 3.0 Nm to 6.0 Nm |
95 mm2 | 6.0 Nm to 12.0 Nm |
150 mm2 | 10.0 Nm to 20.0 Nm |
For frame sizes FX and GX | - | 14.0 Nm to 31.0 Nm |
Weight, approx. | For frame size C | 8.5 kg to 29 kg |
For frame size D | 21 kg to 34 kg |
For frame size E | 49.5 kg to 67 kg |
For frame size F | 67 kg to 77.5 kg |
For frame size FX | 135 kg |
For frame size GX | 138 kg to 208 kg |