Mode of operation |
Measuring principle | Vibrating point level switch |
Input | |
Measured variable | High and low and demand |
Output | |
Output options | - Contactless electronic switch
- Transistor output PNP
|
Measuring accuracy | |
Hysteresis | Approx. 2 mm (0.08 inch) with vertical installation |
Switching delay | Approx. 500 ms (on/off) |
Frequency | Approx. 1 100 Hz |
Rated operating conditions | |
Installation conditions | |
| Indoor/outdoor |
Ambient conditions | |
| -40 ... +70 °C (-40 ... +158 °F) |
| III |
| 2 |
Medium conditions | |
| |
| -40 ... +100 °C (-40 ... +212 °F) |
| -40 ... +150 °C (-40 ... +302 °F) |
| -1 ... 64 bar g (-14.5 ... 928 psi g) |
| 0.7 ... 2.5 g/cm? (0.025 ... 0.09 lb/in?) |
Design | |
Material | |
| 316L and Plastic PEI |
| 316L (1.4404 or 1.4435) |
- Process connection (threaded)
| 316L (1.4404 or 1.4435) |
| Klingersil C-4400 |
Process connection | |
- Pipe thread, cylindrical
(ISO 228 T1)
| G ?" A, G ?" A, or G 1" A |
| ?" NPT, ?" NPT, or 1" NPT |
| Bolting DN 40 PN 40 |
| Tri-clamp 1", 1?", 2" PN 10 |
Degree of protection | IP65/Type 4/NEMA 4 (with DIN 43650 valve plug), IP66/67 or IP68 (with M12 connector) |
Conduit entry | 1 x M12 [IP66/IP67 or IP68 (0.2 bar)] |
Weight (housing) | 250 g (9 oz) |
Power supply | |
Supply voltage | 20 ... 253 V AC, 50/60 Hz 20 ... 253 V DC |
Power consumption | Max. 0.5 W |
Certificates and approvals | - Overfill protection (WHG)
- Shipping approvals
|