General information | | |
Product type designation | CPU 416-3 | CPU416-3 PN/DP |
Engineering with | | |
| STEP 7 V5.3 SP2 or higher with HW update | STEP 7 V5.5 or higher/iMap V3.0 + iMap STEP 7 Add-on V3.0 SP5 or higher |
Supply voltage | | |
Rated value (DC) | | |
| No; Power supply via system power supply | No; Power supply via system power supply |
Power loss | | |
Power loss, typ. | 5.5 W | 6.5 W |
Memory | | |
Work memory | | |
| 11.2 Mbyte | 16 Mbyte |
| 5.6 Mbyte | 8 Mbyte |
| 5.6 Mbyte | 8 Mbyte |
Load memory | | |
| 64 Mbyte | 64 Mbyte |
| 1 Mbyte | 1 Mbyte |
| 64 Mbyte | 64 Mbyte |
CPU processing times | | |
for bit operations, typ. | 30 ns | 30 ns |
for word operations, typ. | 30 ns | 30 ns |
for fixed point arithmetic, typ. | 30 ns | 30 ns |
for floating point arithmetic, typ. | 90 ns | 90 ns |
Counters, timers and their retentivity | | |
S7 counter | | |
| 2 048 | 2 048 |
IEC counter | | |
| Yes | Yes |
S7 times | | |
| 2 048 | 2 048 |
IEC timer | | |
| Yes | Yes |
Data areas and their retentivity | | |
Flag | | |
| 16 kbyte; Size of bit memory address area | 16 kbyte; Size of bit memory address area |
Address area | | |
I/O address area | | |
| 16 kbyte | 16 kbyte |
| 16 kbyte | 16 kbyte |
Process image | | |
| 16 kbyte | 16 kbyte |
| 16 kbyte | 16 kbyte |
Time of day | | |
Clock | | |
| Yes | Yes |
Operating hours counter | | |
| 16 | 16 |
Interfaces | | |
Interfaces/bus type | | 1 x MPI/PROFIBUS DP, 1 x PROFINET (2 ports), 1 x PROFIBUS DP (optionally pluggable) |
Number of RS 485 interfaces | | 0 |
Number of other interfaces | 0 | 0 |
1. Interface | | |
Interface type | Integrated | Integrated |
Physics | RS 485 / PROFIBUS + MPI | RS 485 / PROFIBUS + MPI |
Functionality | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
DP master | | |
| 32 | 32 |
2. Interface | | |
Interface type | Integrated | PROFINET |
Physics | RS 485 / PROFIBUS | Ethernet RJ45 |
Interface types | | |
| | 2 |
Functionality | | |
| | Yes |
| | Yes |
| | Yes |
| Yes | No |
| Yes | No |
DP master | | |
| 125 | |
3. Interface | | |
Interface type | Pluggable interface module (IF), technical data as for 2nd interface | Pluggable interface module (IF) |
Plug-in interface modules | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) | IF 964-DP (MLFB: 6ES7964-2AA04-0AB0) |
Physics | RS 485 / PROFIBUS | RS 485 / PROFIBUS |
Functionality | | |
| No | No |
| Yes | Yes |
| Yes | Yes |
DP master | | |
| 125 | 125 |
Isochronous mode | | |
Isochronous operation (application synchronized up to terminal) | Yes; For PROFIBUS only | Yes; Via PROFIBUS DP or PROFINET interface |
Communication functions | | |
PG/OP communication | Yes | Yes |
Data record routing | Yes | Yes |
Global data communication | | |
| Yes | Yes |
S7 basic communication | | |
| Yes | Yes |
S7 communication | | |
| Yes | Yes |
S5 compatible communication | | |
| Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 | Yes; Via FC AG_SEND and AG_RECV, max. via 10 CP 443-1 or 443-5 |
Standard communication (FMS) | | |
| Yes; Via CP and loadable FB | Yes; Via CP and loadable FB |
Open IE communication | | |
| | Yes; via integrated PROFINET interface and loadable FBs |
| | 94 |
| Via CP 443-1 and loadable FB | Yes; Via integrated PROFINET interface or CP 443-1 and loadable FBs |
| | 94 |
| | Yes; via integrated PROFINET interface and loadable FBs |
| | 94 |
Web server | | |
| No | Yes |
Number of connections | | |
| 64 | 96 |
Ambient conditions | | |
Ambient temperature during operation | | |
| 0 °C; = Tmin | -25 °C; = Tmin |
| 60 °C; = Tmax | 70 °C; = Tmax; @ 60°C for UL/ATEX/FM use |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Extended ambient conditions | | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) | Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) | 100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions) |
Resistance | | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation in corrosive atmospheres! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3C4 incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! | Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Configuration | | |
Know-how protection | | |
| Yes | Yes |
| | Yes; With S7 block Privacy |
Dimensions | | |
Width | 50 mm | 50 mm |
Height | 290 mm | 290 mm |
Depth | 219 mm | 219 mm |
Weights | | |
Weight, approx. | 0.9 kg | 900 g |