Supply voltage | |
Auxiliary voltage 1L+, load voltage 2L+ | |
| 24 V |
Input current | |
from load voltage L+ (without load), max. | 150 mA |
from backplane bus 5 V DC, max. | 100 mA |
Encoder supply | |
Type of output voltage | NAMUR-encoder supply: 8.2 V +/-2% |
Short-circuit protection | Yes |
Output current | |
| 200 mA |
Power loss | |
Power loss, typ. | 10 W |
Digital inputs | |
Number of digital inputs | 8 |
Number of NAMUR inputs | 8 |
Functions | 1 each for gate start/ gate stop |
Input voltage | |
| -3 to +5V |
| 11 to 30.2 V |
Input current | |
| 2 mA |
| 9 mA |
Input delay (for rated value of input voltage) | |
for standard inputs | |
| 50 µs |
Cable length | |
| 100 m |
Digital outputs | |
Number of digital outputs | 8 |
Short-circuit protection | Yes |
Limitation of inductive shutdown voltage to | L+ (-40 V) |
Output voltage | |
| L+ (-0.8 V) |
Output current | |
| 0.5 A |
| 0.5 mA |
Output delay with resistive load | |
| 300 µs |
Switching frequency | |
| 500 Hz |
| 0.5 Hz |
Total current of the outputs (per group) | |
horizontal installation | |
| 4 A |
| 2 A |
all other mounting positions | |
| 2 A |
Cable length | |
| 600 m |
| 100 m |
Encoder | |
Connectable encoders | |
| Yes |
| Yes |
| Yes |
| Yes |
| Yes |
NAMUR encoder | |
| to DIN 19 234 |
| 1.2 mA |
| 2.1 mA |
| 50 µs |
| 20 kHz |
| 100 m |
Interrupts/diagnostics/status information | |
Diagnostic functions | Yes; Diagnostic information readable |
Alarms | |
| Yes; Parameterizable |
| Yes; Parameterizable |
Counter input 24 V | |
| 8; 32 bit or ±31 bit |
| -3 to +5V |
| 11 to 30.2 V |
| 2 mA |
| 9 mA |
| 50 µs |
| 20 kHz; Incremental encoder: 10 kHz |
| 100 m |
Potential separation | |
Potential separation digital inputs | |
| Yes; and shielding |
Potential separation digital outputs | |
| Yes; and shielding |
Potential separation counter | |
| Yes; and shielding |
Standards, approvals, certificates | |
CE mark | Yes |
UL approval | Yes; File E239877 |
FM approval | Yes |
RCM (formerly C-TICK) | Yes |
KC approval | Yes |
EAC (formerly Gost-R) | Yes |
Ambient conditions | |
Ambient temperature during operation | |
| 0 °C; = Tmin |
| 60 °C; = Tmax |
Extended ambient conditions | |
| Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m) |
Relative humidity | |
| 100 %; RH incl. condensation/frost (no commissioning under condensation conditions) |
Resistance | |
| Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation! |
| Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation! |
Connection method | |
required front connector | 1x 40-pin |
Dimensions | |
Width | 80 mm |
Height | 125 mm |
Depth | 120 mm |
Weights | |
Weight, approx. | 460 g |