Medical premises require additional protective measures against the occurrence of excessively high touch voltages. In rooms that conform to Group 2 of DIN VDE 0100-710, any interruption to the examination and /or treatment of patients would place those patients at risk. This is prevented through the use of changeover and monitoring units. These monitor the insulation resistance of the non-grounded IT system, the load current and the temperature of the transformer. A warning signal is output if the limit values are exceeded. This function is carried out by an insulation monitor. In addition, a special voltage relay monitors the voltage of the power supply and switches to a second power supply if it falls below the specified limit values. |