? for signal "0", max. (permissible quiescent current)
0.88 mA
1.1 mA
0.88 mA
? for signal "1", typ.
4 mA
5.5 mA
4.2 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.
1.5 ms
1.5 ms
1.5 ms
— at "1" to "0", max.
1.5 ms
15 ms
1.5 ms
Digital outputs
Number of digital outputs
4
4; Relays
4; Relays
Short-circuit protection
Yes
No
No
Controlling a digital input
Yes
Yes
Switching capacity of the outputs
? on lamp load, max.
1 000 W
1 000 W
Parallel switching of two outputs
? for uprating
No
No
No
Switching frequency
? with resistive load, max.
10 Hz
2 Hz
2 Hz
? with inductive load, max.
0.5 Hz
0.5 Hz
0.5 Hz
? mechanical, max.
10 Hz
10 Hz
Relay outputs
Switching capacity of contacts
— with inductive load, max.
3 A
3 A
— with resistive load, max.
5 A
5 A
— Thermal continuous current, max.
0.3 A
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Yes
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Yes
Yes
Standards, approvals, certificates
CE mark
Yes
Yes
Yes
CSA approval
No
UL approval
No
FM approval
Yes
No
developed in accordance with IEC 61131
Yes
Yes
Yes
according to VDE 0631
Yes
Yes
Marine approval
? Marine approval
Yes
No
Yes
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin; Startup @ -25 °C
-40 °C; = Tmin; Startup @ -25 °C
-40 °C; = Tmin; Startup @ -25 °C
? max.
70 °C; Tmax; Tmax > +55 °C max. load 0.2 A per output
70 °C; = Tmax; Tmax > +55 °C max. load 3 A per relay or max. total current 10 A
70 °C; = Tmax; Tmax > +55 °C max. load 3 A per relay or max. total current 10 A
Ambient temperature during storage/transportation
? min.
-40 °C
-40 °C
-40 °C
? max.
70 °C
70 °C
70 °C
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
? At cold restart, min.
-25 °C
-25 °C
-25 °C
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
35.5 mm
35.5 mm
35.5 mm
Height
90 mm
90 mm
90 mm
Depth
58 mm
58 mm
58 mm
Article number
6AG1055-1FB00-7BA2
6AG1055-1NB10-7BA2
SIPLUS LOGO! DM8 230R V8
SIPLUS LOGO! DM16 24R V8
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
on 35 mm DIN rail, 4 spacing units wide
Supply voltage
Rated value (DC)
? 24 V DC
Yes
? 115 V DC
Yes
? 230 V DC
Yes
permissible range, lower limit (DC)
100 V
20.4 V
permissible range, upper limit (DC)
253 V
28.8 V
Rated value (AC)
? 24 V AC
No
? 115 V AC
Yes
? 230 V AC
Yes
Line frequency
? permissible range, lower limit
47 Hz
? permissible range, upper limit
63 Hz
Digital inputs
Number of digital inputs
4
8
Input voltage
? Type of input voltage
AC/DC
DC
? for signal "0"
< 40 V AC, < 30 V DC
< 5 V DC
? for signal "1"
> 79 V AC, > 79 V DC
> 12 V DC
Input current
? for signal "0", max. (permissible quiescent current)
0.06 mA; 0.05 mA with AC, 0.06 mA with DC
0.85 mA
? for signal "1", typ.
0.37 mA
3.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.
40 ms
1.5 ms
— at "1" to "0", max.
75 ms
1.5 ms
Digital outputs
Number of digital outputs
4; Relays
8; Relays
Short-circuit protection
No
No
Controlling a digital input
Yes
Yes
Switching capacity of the outputs
? on lamp load, max.
1 000 W; 500 W at 115V AC
1 000 W
Parallel switching of two outputs
? for uprating
No
No
Switching frequency
? with resistive load, max.
2 Hz
2 Hz
? with inductive load, max.
0.5 Hz
0.5 Hz
? mechanical, max.
10 Hz
10 Hz
Relay outputs
Switching capacity of contacts
— with inductive load, max.
3 A
3 A
— with resistive load, max.
5 A
5 A
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Yes
Standards, approvals, certificates
CE mark
Yes
Yes
CSA approval
No
UL approval
No
FM approval
No
developed in accordance with IEC 61131
Yes
Yes
according to VDE 0631
Yes
Yes
Marine approval
? Marine approval
No
Yes
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin; Startup @ -25 °C
-40 °C; = Tmin; Startup @ -25 °C
? max.
70 °C; = Tmax; Tmax > +55 °C max. load 3 A per relay or max. total current 10 A
70 °C; = Tmax; Tmax > +55 °C max. load 3 A per relay
Ambient temperature during storage/transportation
? min.
-40 °C
-40 °C
? max.
70 °C
70 °C
Extended ambient conditions
? At cold restart, min.
-25 °C
-25 °C
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
? At cold restart, min.
-25 °C
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
35.5 mm
Height
90 mm
Depth
58 mm
Article number
6AG1055-1MM00-7BA2
SIPLUS LOGO! AM2 AQ V8
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
Supply voltage
Rated value (DC)
? 12 V DC
No
? 24 V DC
Yes
Analog outputs
Number of analog outputs
2
Output ranges, voltage
? 0 to 10 V
Yes
Output ranges, current
? 0 to 20 mA
Yes
? 4 mA to 20 mA
Yes
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Standards, approvals, certificates
CE mark
Yes
developed in accordance with IEC 61131
Yes
according to VDE 0631
Yes
Marine approval
? Marine approval
Yes
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin; Startup @ -25 °C
? max.
70 °C; = Tmax
Ambient temperature during storage/transportation
? min.
-40 °C
? max.
70 °C
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
? At cold restart, min.
-25 °C
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; RH incl. condensation / frost (no commissioning in bedewed state), horizontal installation
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
35.5 mm
Height
90 mm
Depth
58 mm
Article number
6AG1055-1CB00-2BY0
6AG1055-1PB00-2BY0
6AG1055-1HB00-2BY0
6AG1055-1MB00-2BY1
SIPLUS LOGO! DM8 24
SIPLUS LOGO! DM8 12/24
SIPLUS LOGO! DM8 24R
SIPLUS LOGO! DM8 12/24R
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
on 35 mm DIN rail, 2 spacing units wide
on 35 mm DIN rail, 2 spacing units wide
on 35 mm DIN rail, 2 spacing units wide
Supply voltage
Rated value (DC)
? 12 V DC
Yes
? 24 V DC
Yes
Yes
Yes
Yes
permissible range, lower limit (DC)
20.4 V; 22 V @ >55 °C
10.8 V; 11 V @ >55 °C
20.4 V; 22 V @ >55 °C
10.8 V; 11 V @ >55 °C
permissible range, upper limit (DC)
28.8 V; 27.5 V @ >55 °C
28.8 V; 27.5 V @ >55 °C
28.8 V; 27.5 V @ >55 °C
28.8 V; 27.5 V @ >55 °C
Rated value (AC)
? 24 V AC
Yes
Digital inputs
Number of digital inputs
4
4
4
4
Input voltage
? Type of input voltage
DC
DC
AC/DC
DC
Digital outputs
Number of digital outputs
4; Transistor
4; Transistor
4; Relays
4; Relays
Short-circuit protection
Yes
Yes
No
No
Relay outputs
Switching capacity of contacts
— with inductive load, max.
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s
— with resistive load, max.
5 A; 3 A per relay @ > 55 °C; 5 A < 15 s; 10 A all 4 relays in total
5 A; 3 A per relay @ > 55 °C; 5 A < 15 s; 10 A all 4 relays in total
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Yes
Yes
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Yes
Yes
Yes
Standards, approvals, certificates
CSA approval
No
No
No
No
UL approval
Yes; File: E120869 // Tmax = 55 °C
Yes; File: E120869 // Tmax = 55 °C
Yes; File: E120869 // Tmax = 55 °C
Yes; File: E120869 // Tmax = 55 °C
FM approval
No
No
No
No
developed in accordance with IEC 61131
Yes
Yes
Yes
Yes
according to VDE 0631
Yes
Yes
Yes
Yes
Marine approval
? Marine approval
No
No
No
No
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin
-40 °C; = Tmin
-40 °C; = Tmin
-40 °C; = Tmin
? max.
70 °C; = Tmax; 55 °C @ UL/cUL use
70 °C; = Tmax; 55 °C @ UL/cUL use
70 °C; = Tmax; 55 °C @ UL/cUL use
70 °C; = Tmax; 55 °C @ UL/cUL use
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
36 mm; 2 DU
36 mm; 2 DU
36 mm; 2 DU
36 mm; 2 DU
Height
90 mm
90 mm
90 mm
90 mm
Depth
55 mm
55 mm
55 mm
55 mm
Article number
6AG1055-1FB00-2BY1
6AG1055-1NB10-2BA0
SIPLUS LOGO! DM8 230R
SIPLUS LOGO! DM16 24R ERW.-MODUL
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
on 35 mm DIN rail, 4 spacing units wide
Supply voltage
Rated value (DC)
? 24 V DC
Yes
? 115 V DC
Yes
? 230 V DC
Yes
permissible range, lower limit (DC)
100 V
20.4 V; 22 V @ >55 °C
permissible range, upper limit (DC)
253 V
28.8 V; 27.5 V @ >55 °C
Rated value (AC)
? 115 V AC
Yes
? 230 V AC
Yes
Digital inputs
Number of digital inputs
4
8
Input voltage
? Type of input voltage
AC/DC
DC
? for signal "0"
< 5 V DC
? for signal "1"
> 12 V DC
Input current
? for signal "0", max. (permissible quiescent current)
1 mA
? for signal "1", typ.
2 mA
Input delay (for rated value of input voltage)
for standard inputs
— at "0" to "1", max.
1.5 ms
— at "1" to "0", max.
1.5 ms
Digital outputs
Number of digital outputs
4; Relays
8; Relays
Short-circuit protection
No
No
Controlling a digital input
Yes
Switching capacity of the outputs
? on lamp load, max.
1 000 W; 500 W at 115V AC
Parallel switching of two outputs
? for uprating
No
Switching frequency
? with resistive load, max.
2 Hz
? with inductive load, max.
0.5 Hz
? mechanical, max.
10 Hz
Relay outputs
Switching capacity of contacts
— with inductive load, max.
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s
3 A; 1 A per relay @ > 55 °C; 3 A per relay @ > 55 °C & < 15 s
— with resistive load, max.
5 A; 3 A per relay @ > 55 °C; 5 A < 15 s; 10 A all 4 relays in total
5 A; 3 A per relay @ > 55 °C; 10 A per relay @ > 55 °C & < 15 s
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Yes
Standards, approvals, certificates
CSA approval
No
No
UL approval
Yes; File: E120869 // Tmax = 55 °C
In application process
FM approval
No
No
developed in accordance with IEC 61131
Yes
Yes
according to VDE 0631
Yes
Yes
Marine approval
? Marine approval
No
No
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin
-25 °C; = Tmin
? max.
70 °C; = Tmax; 55 °C @ UL/cUL use
70 °C; = Tmax; 55 °C @ UL/cUL use
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m)
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
36 mm; 2 DU
72 mm; 4 WU
Height
90 mm
90 mm
Depth
55 mm
53 mm
Article number
6AG1055-1MA00-2BY0
SIPLUS LOGO! AM2
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
Supply voltage
Rated value (DC)
? 12 V DC
Yes
? 24 V DC
Yes
Analog inputs
Number of analog inputs
2
Input ranges
? Voltage
Yes
? Current
Yes
? Resistance thermometer
No
Input ranges (rated values), voltages
? 0 to +10 V
Yes
Input ranges (rated values), currents
? 0 to 20 mA
Yes
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Standards, approvals, certificates
CSA approval
No
UL approval
Yes; File: E120869 // Tmax = 55 °C
FM approval
No
developed in accordance with IEC 61131
Yes
according to VDE 0631
Yes
Marine approval
? Marine approval
No
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin
? max.
70 °C; = Tmax; 55 °C @ UL/cUL use
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
36 mm
Height
90 mm
Depth
55 mm
Article number
6AG1055-1MM00-2BY1
SIPLUS_LOGO!_AM2_AQ
Installation type/mounting
Mounting
on 35 mm DIN rail, 2 spacing units wide
Supply voltage
Rated value (DC)
? 24 V DC
Yes
Analog outputs
Number of analog outputs
2
Output ranges, voltage
? 0 to 10 V
Yes
Output ranges, current
? 0 to 20 mA
Yes
? 4 mA to 20 mA
Yes
EMC
Emission of radio interference acc. to EN 55 011
? Limit class B, for use in residential areas
Yes; Radio interference suppression according to EN55011, Limit Value Class B
Degree and class of protection
Degree of protection acc. to EN 60529
? IP20
Yes
Standards, approvals, certificates
CSA approval
No
UL approval
No
FM approval
No
developed in accordance with IEC 61131
Yes
according to VDE 0631
Yes
Marine approval
? Marine approval
No
Ambient conditions
Ambient temperature during operation
? min.
-40 °C; = Tmin
? max.
70 °C; = Tmax; 55 °C @ UL/cUL use
Extended ambient conditions
? relative to ambient temperature-atmospheric pressure-installation altitude
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
Relative humidity
— With condensation, tested in accordance with IEC 60068-2-38, max.
100 %; Relative humidity, incl. condensation / frost permitted (no commissioning under condensation conditions)
Resistance
— against biologically active substances / conformity with EN 60721-3-3
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
— against chemically active substances / conformity with EN 60721-3-3
Yes; Class 3C4 incl. salt spray. The supplied connector covers must remain on the unused interfaces during operation!
— against mechanically active substances / conformity with EN 60721-3-3
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
Dimensions
Width
36 mm
Height
90 mm
Depth
55 mm
skener.ru
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Àðìàòóðà DENDOR
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Äàò÷èêè è èçìåðèòåëè
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ðåãóëÿòîðû è ðåãèñòðàòîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ïíåâìàòè÷åñêîå îáîðóäîâàíèå
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Êðàíû è Êëàïàíû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Èçìåðèòåëüíûå ïðèáîðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Ñèñòåìû áåñïðîâîäíîãî óïðàâëåíèÿ «óìíûé äîì»
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Áåñêîíòàêòíûå âûêëþ÷àòåëè Êîíå÷íûå âûêëþ÷àòåëè Îïòè÷åñêèå äàò÷èêè Ýíêîäåðû
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FS - Óñòàíîâêà óìÿã÷åíèÿ
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 23
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
Deprecated: Function eregi() is deprecated in /home/h101150-2/siemens71.ru/docs/kip/kip.php on line 30
SKW-FK - Óñòàíîâêà îáåçæåëåçèâàíèÿ