Integration in automation systems | |
S7-400, S7-300, C7 | Through ET 200S |
Automation systems from other vendors | Possible through ET 200S with IM 151-1 |
Communication interfaces | SIMATIC S7 (ET 200S backplane bus), 8 bytes, I/O area |
Module parameterization | Not required (module is pre-parameterized) |
Measuring properties | |
Error limit to DIN 1319-1 of full-scale value at 20 °C ± 10 K (68 °F ± 10 K) | ? 0.15 % |
Signal resolution | 14 bits plus 1 bit sign |
Number of measurements/second | 50 |
Low-pass filter | Without or 2 Hz |
Sensors | In accordance with the principle of expansion measurement (full bridge) 4-wire connection |
Sensor feed | |
Supply voltage, short-circuit-proof | 6 V DC ± 5 % |
Permissible sensor resistance | |
| > 250 ? |
| < 4010 ? |
Permissible sensor cell coefficient | Up to 4 mV/V |
Permissible range of the measuring signal | -25.2 ... +25.2 mV |
Auxiliary power supply | |
Rated voltage | 24 V DC |
Max. current consumption | 150 mA |
Current consumption on backplane bus | typ. 10 mA |
Connection to sensors in Ex zone 1 | Optionally via SIWAREX IS Ex interface |
Ex approval zone 2 and safety | ATEX 95, cULus Haz. Loc. |
IP degree of protection to EN 60529; IEC 60529 | IP20 |
Climatic requirements Tmin (IND) to Tmax (IND) (operating temperature) | |
| 0 ... +60 °C (32 ... +140 °F) |
| 0 ... +40 °C (32 ... 104 °F) |
EMC requirements according to | NAMUR NE21, Part 1 89/386/EEC |
Dimensions | 30 x 80 x 50 mm (1.18 x 3.15 x 1.97 inch) |