Supply voltage | | |
Rated value (DC) | 24 V | 24 V |
Reverse polarity protection | Yes; against destruction | Yes; against destruction |
Short-circuit protection | Yes; over exchangeable fuses | Yes; over exchangeable fuses |
Load voltage 2L+ | | |
| 24 V | 24 V |
| Yes; against destruction | Yes; against destruction |
Input current | | |
from supply voltage 1L+, max. | 200 mA | 200 mA |
Power loss | | |
Power loss, typ. | 5 W | 5 W |
Address area | | |
Addressing volume | | |
| 244 byte | 244 byte |
| 244 byte | 244 byte |
Interfaces | | |
Interfaces/bus type | PROFIBUS DP | PROFIBUS DP |
Interface physics, RS 485 | Yes | Yes |
PROFIBUS DP | | |
| Yes | Yes |
| 9.6 kbit/s | 9.6 kbit/s |
| 12 Mbit/s | 12 Mbit/s |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Interrupts/diagnostics/status information | | |
Alarms | | |
| Yes; Parameterizable | Yes; Parameterizable |
| Yes; Parameterizable | Yes; Parameterizable |
Diagnostics indication LED | | |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
| Yes | Yes |
Parameter | | |
DPV1 operation | possible | possible |
Swapping interrupt | Parameterizable | Parameterizable |
Startup if setpoint not equal to actual configuration | Parameterizable | Parameterizable |
Potential separation | | |
between supply voltage and electronics | Yes | Yes |
Isolation | | |
Isolation tested with | 707 V DC (type test) | 707 V DC (type test) |
Degree and class of protection | | |
Degree of protection acc. to EN 60529 | | |
| Yes | Yes |
Ambient conditions | | |
Ambient temperature during operation | | |
| -25 °C | -25 °C |
| 55 °C | 55 °C |
Ambient temperature during storage/transportation | | |
| -40 °C | -40 °C |
| 70 °C | 70 °C |
Dimensions | | |
Width | 90 mm | 90 mm |
Height | 130 mm | 130 mm |
Depth | 59.3 mm | 59.3 mm |
Weights | | |
Weight, approx. | 375 g | 375 g |