Input | |
Resistance thermometer | |
Measured variable | Temperature |
Sensor type | |
| Pt25 … Pt1000 |
- Acc. to JIS C 1604; a=0.00392 K-1
| Pt25 … Pt1000 |
| Ni25 … Ni1000 |
Units | °C and °F |
Connection | |
| 1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system |
| Series or parallel connection of several resistance thermometers in a two-wire system for the generation of average temperatures or for adaptation to other device types |
| 2 resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) |
Connection | |
| Line resistance can be configured ?100 ? (loop resistance) |
| No trim necessary |
| No trim necessary |
Sensor current | ? 0.45 mA |
Response time | ? 250 ms for 1 sensor with break monitoring |
Break monitoring | Always active (cannot be switched off) |
Short-circuit monitoring | Can be switched on/off (default value: ON) |
Measuring range | Assignable (see "Digital measuring error" table) |
Min. measuring span | 10 °C (18 °F) |
Characteristic curve | Temperature-linear or special characteristic |
Resistance-based sensor | |
Measured variable | Actual resistance |
Sensor type | Resistance-based, potentiometers |
Units | ? |
Connection | |
| 1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system |
| 2 resistance-based sensors in 2-wire system for generation of average value |
| 2 resistance-based sensor in 2-wire system (R 1 – R 2 or R 2 – R 1) |
Connection | |
| Line resistance can be configured ?100 ? (loop resistance) |
| No trim necessary |
| No trim necessary |
Sensor current | ? 0.45 mA |
Response time | ? 250 ms for 1 sensor with break monitoring |
Break monitoring | Can be switched off |
Short-circuit monitoring | Can be switched off (value is adjustable) |
Measuring range | Assignable max. 0 ... 2200 ? (see "Digital measuring error" table) |
Min. measuring span | 5 ... 25 ? (see "Digital measuring error" table) |
Characteristic curve | Resistance-linear or special characteristic |
Thermocouples | |
Measured variable | Temperature |
Sensor type (thermocouples) | |
| Pt30Rh-Pt6Rh acc. to IEC 584 |
| W5%-Re acc. to ASTM 988 |
| W3%-Re acc. to ASTM 988 |
| NiCr-CuNi acc. to IEC 584 |
| Fe-CuNi acc. to IEC 584 |
| NiCr-Ni acc. to IEC 584 |
| Fe-CuNi acc. to DIN 43710 |
| NiCrSi-NiSi acc. to IEC 584 |
| Pt13Rh-Pt acc. to IEC 584 |
| Pt10Rh-Pt acc. to IEC 584 |
| Cu-CuNi acc. to IEC 584 |
| Cu-CuNi acc. to DIN 43710 |
Units | °C or °F |
Connection | |
| 1 thermocouple (TC) |
| 2 thermocouples (TC) |
| 2 thermocouples (TC) (TC 1 – TC 2 or TC 2 – TC 1) |
Response time | ? 250 ms for 1 sensor with break monitoring |
Break monitoring | Can be switched off |
Reference junction compensation | |
| With integrated Pt100 resistance thermometer |
| With external Pt100 IEC 60751 (2-wire or 3-wire connection) |
| Reference junction temperature can be set as fixed value |
Measuring range | Assignable (see "Digital measuring error" table) |
Min. measuring span | Min. 40 ... 100 °C (72 ... 180 °F) (see "Digital measuring error" table) |
Characteristic curve | Temperature-linear or special characteristic |
mV sensor | |
Measured variable | DC voltage |
Sensor type | DC voltage source (DC voltage source possible over an externally connected resistor) |
Units | mV |
Response time | ? 250 ms for 1 sensor with break monitoring |
Break monitoring | Can be switched off |
Measuring range | -10 ... +70 mV -100 ... +1100 mV |
Min. measuring span | 2 mV or 20 mV |
Overload capability of the input | -1.5 ... +3.5 V DC |
Input resistance | ? 1 M? |
Characteristic curve | Voltage-linear or special characteristic |
Output | |
Output signal | 4 ... 20 mA, 2-wire |
Communication with SITRANS TH300 | According to HART Rev. 5.9 |
digital display | |
Digital display (optional) | In current loop |
Display | Max. 5 digits |
Digit height | 9 mm (0.35“) |
Display range | -99 999 ... +99 999 |
Units | Any (max. 5 char.) |
Setting: Zero point, full-scale value and unit | Using 3 buttons |
Load voltage | 2.1 V |
Measuring accuracy | |
Digital measuring error | See "Digital measuring error" table |
Reference conditions | |
| 24 V ± 1 % |
| 500 ? |
| 23 °C (73.4 °F) |
| > 5 min |
Error in the analog output (digital/analog converter) | < 0.025 % of measuring span |
Error due to internal reference junction | < 0.5 °C (0.9 °F) |
Effect of ambient temperature | |
| 0.02 % of meas. span/10 °C (18 °F) |
| |
- with resistance thermometers
| 0.06 °C (0.11 °F)/10°C (18 °F) |
| 0.6 °C (1.1 °F)/10°C (18 °F) |
Auxiliary power effect | < 0.001 % of meas. span/V |
Effect of load impedance | < 0.002 % of meas. span/100 ? |
Long-term drift | |
| < 0.02 % of measuring span |
| < 0.2 % of measuring span |
| < 0.3 % of measuring span |
Conditions of use | |
Ambient conditions | |
Ambient temperature | -40 ... +85 °C (-40 ... +185 °F) |
Condensation | Permissible |
Electromagnetic compatibility | According to EN 61326 and NAMUR NE21 |
Degree of protection acc. to EN 60529 | IP66/67/68 |
Design | |
Weight | Approx. 1.5 kg (3.3 lb) without options |
Dimensions | See "Dimensional drawings" |
Enclosure material | Die-cast aluminum, low in copper, GD?AlSi 12 or stainless steel, polyester-based lacquer, stainless steel rating plate |
Electrical connection, sensor connection | Screw terminals, cable inlet via M20 x 1.5 or ?-14 NPT screwed gland |
Mounting bracket (optional) | Steel, galvanized and chrome-plated or stainless steel |
Auxiliary power | |
Without digital display | 11 ... 35 V DC (30 V with Ex ib; 32 V with Ex ic and Ex nA) |
With digital display | 13.1 ... 35 V DC (30 V with Ex ib; 32 V with Ex ic and Ex nA) |
Electrical isolation | Between input and output |
| Ueff = 1 kV, 50 Hz, 1 min |
Certificates and approvals | |
Explosion protection ATEX | |
- "Intrinsic safety" type of protection
| With digital display: II 2 (1) G Ex ib [ia Ga] IIC T4 Gb II 2 G Ex ib IIC T4 Gb II 1D Ex ia IIIC T100 °C Da Without digital display: II 2 (1) G Ex ib [ia Ga] IIC T6 Gb II 2 G Ex ib IIC T6 Gb II 1D Ex ia IIIC T100 °C Da |
- EC type-examination certificate
| ZELM 11 ATEX 0471 X |
- "Non-sparking and energy-limited equipment for Zone 2" type of protection
| II 3 G Ex ic IIC T6/T4 Gc II 3 G Ex nA IIC T6/T4 Gc II 3 G Ex nA [ic] IIC T6/T4 Gc |
- EC type-examination certificate
| ZELM 11 ATEX 0471 X |
- "Flameproof enclosure" type of protection
| II 2 G Ex d IIC T6/T5 Gb II 2 D Ex tb IIIC T100 °C Db |
- EC type-examination certificate
| ZELM 11 ATEX 0472 X |
Explosion protection acc. to FM | Certificate of Compliance 3017742 |
- Identification (XP, DIP, NI, S)
| - XP/I/1/BCD/T5 Ta = 85 °C (185 °F), T6 Ta = 60 °C (140 °F), Type 4X
|
| - DIP/II, III/1/EFG/T5 Ta = 85 °C (185 °F), T6 Ta = 60 °C (140 °F), Type 4X
|
| - NI/I/2/ABCD/T5 Ta = 85 °C (185 °F), T6 Ta = 60 °C (140 °F), Type 4X
|
| - S/II, III/2/FG/T5 Ta = 85 °C (185 °F), T6 Ta = 60 °C (140 °F), Type 4X
|
Other certificates | IECEx, EAC Ex(GOST), INMETRO, NEPSI, KOSHA |
Hardware and software requirements | |
- For the SIPROM T parameterization software for SITRANS TF with TH200
| |
| PC with CD-ROM drive and USB interface |
| Windows 98, NT, 2000, XP, 7 and Win 8 |
- For the SIMATIC PDM parameterization software for SITRANS TH300
| See chapter 8 "Software", "SIMATIC PDM" |
Communication | |
Load for HART connection | 230 ... 1100 ? |
| ? 3.0 km (1.86 mi) |
| ? 1.5 km (0.93 mi) |
Protocol | HART protocol, version 5.9 |