SITRANS TH100 | |
Input | |
Resistance thermometer | |
Measured variable | Temperature |
Sensor type | Pt100 according to IEC 60751 |
Characteristic curve | Linear to temperature |
Type of connection | 2-, 3- or 4-wire system |
Resolution | 14 bit |
Measuring accuracy | |
| < 0.25 °C (0.45 °F) |
| < 0.1 % of measuring span |
Repeatability | < 0.1 °C (0.18 °F) |
Measuring current | approx. 0.4 mA |
Measuring cycle | < 0.7 s |
Measuring range | -200 ... +850 °C (-328 ... +1562 °F) |
Measuring span | 25 ... 1050 °C (77 ... 1922 °F) |
Unit | °C or °F |
Offset | Programmable: -100 ... +100 °C (-180 ... +180 °F) |
Line resistance | Max. 20 ? (total from feeder and return conductor) |
Noise rejection | 50 and 60 Hz |
Output | |
Output signal | 4 ... 20 mA, two-wire |
Auxiliary power | 8.5 ... 36 V DC (30 V with Ex ia and ib; 32 V with Ex nL/ic; 35 V with Ex nA) |
Max. load | (Uaux – 8.5 V)/0.023 A |
Overrange | 3.6 ... 23 mA, infinitely adjustable (default range: 3.84 ... 20.5 mA) |
Error signal (following sensor fault) (conforming to NE43) | 3.6 ... 23 mA, infinitely adjustable (default range: 3.6 mA or 22.8 mA) |
Damping time | 0…30 s (default value: 0 s) |
Protection | Against reverse polarity |
Resolution | 12 bit |
Accuracy at 23 °C (73.4 °F) | < 0.1 % of measuring span |
Temperature effect | < 0.1 %/10 °C (0.1 %/18 °F) |
Effect of auxiliary power | < 0.01 % of span/V |
Effect of load impedance | < 0.025 % of max. span/100 ? |
Long-term drift | - < 0.025 % of the max. span in the first month
|
| - < 0.035 % of the max. span after one year
|
| - < 0.05 % of the max. span after 5 years
|
Ambient conditions | |
Ambient temperature | -40 ... +85 °C (-40 ... +185 °F) |
Storage temperature | -40 ... +85 °C (-40 ... +185 °F) |
Relative humidity | < 98 %, with condensation |
Electromagnetic compatibility | According to EN 61326 and NAMUR NE21 |
Design | |
Weight | 50 g |
Dimensions | See dimensional drawing |
Material | Molded plastic |
Cross-section of cables | Max. 2.5 mm2 (AWG 13) |
Degree of protection according to IEC 60529 | |
| IP40 |
| IP00 |
Certificates and approvals | |
Explosion protection ATEX | |
EC type-examination certificate | PTB 05 ATEX 2049X |
- "Intrinsic gas safety" type of protection
| II 1 G Ex ia IIC T6/T4 II (1) 2 G Ex ib [ia Ga] IIC T6/T4 Gb II (1) 3 G Ex ic [ia Ga] IIC T6/T4 Gc II 3 G Ex ic IIC T6/T4 Gc |
- "Non-sparking" type of protection
| II 3 G Ex nA IIC T6/T4 Gc II 3 G Ex nA [ic] IIC T6/T4 Gc |
- "Intrinsic dust safety" type of protection
| II 1 D Ex ia IIIC T115 °C Da |
Explosion protection: FM for USA | |
| FM 3024169 |
| IS / Cl I, II, III / Div 1 / GP ABCDEFG T6, T5, T4 Cl I / ZN 0 / AEx ia IIC T6, T5, T4 NI / Cl I / Div 2 / GP ABCDFG T6, T5, T4 NI / Cl I / ZN 2 / IIC T6, T5, T4 |
Explosion protection to FM for Canada (cFMUS) | |
| FM 3024169C |
| IS / Cl I, II, III / Div 1/ GP ABCDEFG T6, T5, T4 NI / Cl I / DIV 2 / GP ABCD T6, T5, T4 NIFW / Cl I, II, III / DIV 2 / GP ABCDFG T6, T5, T4 DIP / Cl II, III / Div 2 / GP FG T6, T5, T4 Cl I / ZN 0 / Ex ia IIC T6, T5, T4 Cl I / ZN 2 / Ex nA nL IIC T6, T5, T4 |
Other certificates | EAC Ex(GOST), NEPSI |
Software requirements for SIPROM T | |
PC operating system | Windows ME, 2000, XP, Win 7 and Win 8; in connection with RS 232 modem, also Windows 95, 98 and 98SE |
Factory setting: | |
- Pt100 (IEC 751) with 3-wire system
- Measuring range: 0 ... 100 °C (32 ... 212 °F)
- Error signal in the event of sensor breakage: 22.8 mA
- Sensor offset: 0 °C (0 °F)
- Damping 0.0 s
|