Input | |
Selectable filters to suppress the line frequency | 50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) |
Resistance thermometer | |
Measured variable | Temperature |
Measuring range | Assignable |
Span | Min. 25 °C (45 °F) x 1/scaling factor |
Sensor type | |
| Pt100 (IEC 751) |
| Pt100 (JIS C1604-81) |
| Ni100 (DIN 43760) |
- Special type (RRTD ? 500 ?)
| Multiples or fractions of the specified basic values can be assigned (e.g. Pt500, Ni120) |
Characteristic curve | Temperature-linear, resistance-linear or customer-specific |
Type of connection | - Normal connection
- Sum or parallel connection
- Mean-value or differential connection
|
Connection | 2, 3 or 4-wire system |
Measuring range limits | Depending on type of connected thermometer (defined range of resistance thermometer) |
Sensor breakage monitoring | Monitoring of all connections for wire break (function can be switched off) |
Sensor short-circuit monitoring | Configurable response threshold (function can be switched off) |
Resistance-based sensor, potentiometer | |
Measured variable | Actual resistance |
Measuring range | Assignable |
Span | Min. 10 ? |
Characteristic curve | Resistance-linear or customer-specific |
Type of connection | - Normal connection
- Differential connection
- Mean-value connection
|
Connection | 2, 3 or 4-wire system |
Input range | 0 ... 6000 ?; with mean-value and difference circuits: 0 ... 3000 ? |
Sensor breakage monitoring | Monitoring of all connections for wire break (function can be switched off) |
Sensor short-circuit monitoring | Configurable response threshold (function can be switched off) |
Thermocouples | |
Measured variable | Temperature |
Measuring range | Assignable |
Span | Min. 50 ? (90 °F) x 1/scaling factor |
Measuring range limits | Depending on type of thermocouple element |
Thermocouple element | |
| Pt30 %Rh/Pt6 %Rh (DIN IEC 584) |
| W5%-Re (ASTM 988) |
| W3%-Re (ASTM 988) |
| NiCr/CuNi (DIN IEC 584) |
| Fe/CuNi (DIN IEC 584) |
| NiCr/Ni (DIN IEC 584) |
| Fe-CuNi (DIN 43710) |
| NiCrSi-NiSi (DIN IEC 584) |
| Pt13 %Rh/Pt (DIN IEC 584) |
| Pt10 %Rh/Pt (DIN IEC 584) |
| Cu/CuNi (DIN IEC 584) |
| Cu/CuNi (DIN 43710) |
| Special type (-10 mV ? UTC ? 100 mV) |
Characteristic curve | Temperature-linear, voltage-linear or customer-specific |
Type of connection | - Normal connection
- Averaging connection
- Mean-value connection
- Differential connection
|
Reference junction compensation | None, device-internal measurement, external measurement or predefined fixed value |
Sensor breakage monitoring | Function can be switched off |
mV sensors | |
Measured variable | DC voltage |
Measuring range | Assignable |
Span | Min. 4 mV |
Input range | -120 ... +1000 mV |
Characteristic curve | Voltage-linear or customer-specific |
Overload capacity of inputs | Max. ± 3.5 V |
Input resistance | ? 1 M? |
Sensor current | Approx. 180 ?A |
Sensor breakage monitoring | Function can be switched off |
V sources | |
Measured variable | DC voltage |
Measuring range | Assignable |
Characteristic curve | Voltage-linear or customer-specific |
Input range/min. Span | |
- Devices with 7NG3242-xxxx1 or 7NG3242-xxxx0 with U/I plug
| -1.2 ... + 10 V/0.04 V |
- Devices with 7NG3242-xxxx2
| -12 ... +100 V/0.4 V |
- Devices with 7NG3242-xxxx3
| -120 V ... +140 V/4.0 V |
Sensor breakage monitoring | Not possible |
?A-, mA sources | |
Measured variable | DC voltage |
Measuring range | Assignable |
Characteristic curve | Current-linear or customer-specific |
Input range/min. Span | |
- Devices with 7NG3242-xxxx4
| -12 ?A ... +100 ?A/0.4 ?A |
- Devices with 7NG3242-xxxx5
| -120 ?A ... +1000 ?A/4 ?A |
- Devices with 7NG3242-xxxx6
| -1.2 mA ... +10 mA/0.04 mA |
- Devices with 7NG3242-xxxx7 or 7NG3242-xxxx0 with U/I plug
| -12 mA ... +100 mA/0.4 mA |
- Devices with 7NG3242-xxxx8
| -120 mA ... +1000 mA/4 mA |
Sensor breakage monitoring | Not possible |
Output | |
Output signal | Load-independent direct current 0/4 ... 20 mA, can be switched to load-independent DC voltage 0/2 ... 10 V using plug-in jumpers |
Current 0/4 ... 20 mA | |
| -0.5 ... +23.0 mA, infinitely adjustable |
- Output range following sensor fault (conforming to NE43)
| -0.5 ... +23.0 mA, infinitely adjustable |
| ? 650 ? |
| ? 30 V |
Voltage 0/2 ... 10 V | |
| -0.25 ... +10.75 V, infinitely adjustable |
- Output range following sensor fault
| -0.25 ... +10.75 V, infinitely adjustable |
| ? 1 k? |
| ? 10 nF |
| ? 100 mA (not permanently short-circuit-proof) |
| |
- adjustable time constant T63
| 0 ... 100 s, in steps of 0.1 s |
- Current source/voltage source
| Infinitely adjustable within the entire operating range |
Sensor fault/limit signaling | By operation indicator, relay output or HART interface |
Operation indicator | Flashing signal |
| Flashing frequency 5 Hz |
| Flashing frequency 1 Hz |
Relay outputs | Either as NO or NC contact with 1 changeover contact |
| ? 150 W, ? 625 VA |
| ? 125 V DC, ? 250 V AC |
| ? 2.5 A DC |
Sensor fault | Signalling of sensor or line breakage and sensor short-circuit |
Limit monitoring | |
| 0 ... 10 s |
- Monitoring functions of limit module
| - Sensor fault (breakage and/or short-circuit)
- Lower and upper limit
- Window (combination of lower and upper limits)
- Limit and sensor fault detection can be combined
|
| Configurable between 0 and 100 % of measuring range |
Auxiliary power | |
Universal power supply unit | 115/230 V AC/DC or 24 V AC/DC |
Tolerance range for power supply | |
| 80 ... 300 V DC; 90 ... 250 V AC |
| 18 ... 80 V DC; 20.4 ... 55.2 V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range) |
Tolerance range for mains frequency | 47 ... 63 Hz |
Power consumption with | |
| ? 5 VA |
| ? 5 W |
| ? 5 VA |
| ? 5 W |
Electrical isolation | |
Electrically isolated circuits | Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. |
Working voltage between all electrically isolated circuits | The voltage Urms between any two terminals must not exceed 300 V |
Measuring accuracy | |
Accuracy | |
- Error in the internal reference junction
| ? 3 °C ± 0.1 °C / 10 °C (? 5.4 °F ± 0.18 °F / 18 °F) |
- Error of external reference junction terminal 7NG3092-8AV
| ? 0.5 °C ± 0.1 °C / 10 °C (? 0.9 °F ± 0.18 °F / 18 °F) |
| See "Digital error" |
| ? 0.05 % of meas. span plus digital error |
Influencing effects (referred to the digital output) | Compared to the max. measuring span: |
| ? 0.08 % / 10 °C (? 0.08 % / 18 °F) ? 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
| ? 0.1 % / year |
Influencing effects referred to the analog output IAN or UAN | Compared to the measuring span: |
| ? 0.08 % / 10°C (? 0.08 % / 18 °F) ? 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
| ? 0.05 % / 10 V |
| ? 0.05 % on change from 50 ? to 650 ? |
| ? 0.1 % on change in the load current from 0 mA to 10 mA |
- Long-term drift (start-of-scale value, measuring span)
| ? 0.03 % / month |
Response time (T63 without electrical damping) | ? 0.2 s |
Insulation tests | |
Auxiliary power relative to input and output | 3.54 kV DC; 2 s |
Input relative to output and limit monitor | 2.13 kV DC; 2 s |
Output relative to limit monitor | 2.13 kV DC; 2 s |
PE/ground conductor relative to auxiliary power, input, output, and limit monitor | 0.71 kV AC; 2 s |
Electromagnetic compatibility | According to EN 61326 and NAMUR NE21 |
Certificates and approvals | |
Intrinsic safety | |
| II (1) G [Ex ia Ga] IIC |
| II (1) D [Ex ia Da] IIIC |
EC type-examination certificate | TUV (German Technical Inspectorate) 01 ATEX 1675 |
Other certificates | EAC Ex (GOST) |
Conditions of use | |
Installation conditions | |
Location (for devices with explosion protection) | |
| Outside the hazardous area |
| Within hazardous area Zone 1 (also in Zone 0 in conjunction with the prescribed protection requirements for the sensor) |
Ambient conditions | |
Ambient temperature | -25 ... +70 °C (-13 ... +158 °F) |
Storage temperature | -40 ... +85 °C (-40 ... +185 °F) |
Climatic class | |
| 5 ... 95 %, no condensation |
Design | |
Weight | Approx. 0.24 kg (0.53 lb) |
Enclosure material | PBT, glass-fibre reinforced |
Degree of protection according to IEC 529 | IP20 |
Degree of protection according to VDE 0100 | Protection class I |
Type of installation | 35-mm DIN rail (1.38 inch) (EN 50022) or 32-mm G-type rail (1.26 inch) (EN 50035) |
Electrical connection / process connection | Screw plug connectors, max. 2.5 mm? (0.01 inch?) |
Parameterization interface | |
Protocol | HART, version 5.9 |
Load with connection of | |
| 230 ... 650 ? |
| 230 ... 500 ? |
Software for PC/laptop | SIMATIC PDM version V5.1 and later |