Mode of operation | |
Measuring principle | Radar level measurement |
Frequency | 5.8 GHz (North America 6.3 GHz) |
Measuring range | 0.3 ... 20 m (1.0 ... 65 ft) |
Output | |
Analog output | 4 ... 20 mA |
Accuracy | ± 0.02 mA |
Span | Proportional or inversely proportional |
Communications | HART Optional: PROFIBUS PA (Profile 3.0, Class B) |
Fail-safe | Programmable as high, low or hold (Loss of Echo) |
Performance (according to reference conditions IEC60770-1) |
From end of antenna to 600 mm | 40 mm (1.57 inch) |
Remainder of range | 10 mm (0.4 inch) or 0.1 % of span (whichever is greater) |
Rated operating conditions | |
Installation conditions | |
| Indoor/outdoor |
Ambient conditions (enclosure) | |
| -40 ... +80 °C (-40 ... +176 °F) |
| I |
| 4 |
Medium conditions | |
Dielectric constant ?r | ?r > 1.6 (for ?r < 3, use stillpipe) |
Vessel temperature and pressure | Varies with connection type; see Pressure/Temperature curves for more information |
Design | |
Enclosure | |
| Aluminum, polyester powder coated |
| 2 x M20 x 1.5 or 2 x ?" NPT |
Degree of protection | Type 4X/NEMA 4X, Type 6/ NEMA 6, IP67, IP68 |
Weight | < 2.82 kg (6.21 lb) (polypropylene rod antenna) |
Display (local) | Multi-segment alphanumeric liquid crystal with bar graph (representing level) available in four languages |
Antenna | |
| Polypropylene rod, hermetically sealed construction, optional PTFE |
| Standard 100 mm (4 inch) shield for maximum 100 mm (4 inch) nozzle, or optional 250 mm (10 inch) long shield |
| Refer to SITRANS LR200 Antennas for optional rods and horns |
Process connections | |
| 1?" NPT [(Taper), ANSI/ASME B1.20.1] R 1?" [(BSPT), EN 10226], or G 1?" [(BSPP), EN ISO 228-1] (polypropylene rod antenna) |
| Refer to SITRANS LR200 Antennas for more connections |
Power supply | |
4 ... 20 mA/HART | |
- General Purpose, Non-incendive, Intrinsically Safe
| Nominal 24 V DC (max. 30 V DC) with max. 550 ? |
- Flame proof, Increased safety, Explosion proof
| Nominal 24 V DC (max. 30 V DC) with max. 250 ? |
PROFIBUS PA | |
Certificates and approvals | |
General | CSAUS/C, CE, FM, RCM |
Marine | - Lloyd’s Register of Shipping
- ABS Type Approval
|
Radio | FCC, Industry Canada, and European (R&TTE), RCM |
Hazardous | |
- Intrinsically Safe (Brazil)
| INMETRO Ex ia IIC T4 Ga |
- Explosion Proof (Canada/USA)
| CSA/FM, Class I, Div. 1, Groups A, B, C, D; Class II, Div. 1, Groups E, F, G; Class III, T4 |
- Intrinsically Safe (Canada/USA)
| CSA/FM, Class I, Div. 1, Groups A, B, C, D; Class II, Div. 1, Groups E, F, G; Class III, T4 |
| FM, Class I, Div. 2, Groups A, B, C, D, T5 |
- Flame Proof/Increased Safety (China)
| NEPSI Ex d mb ia IIC T4/ Ex e mb ia IIC T4 |
| ATEX II 1/2 G Ex d mb ia IIC T4 Ga/Gb |
- Increased Safety (Europe)
| ATEX II 1/2 G Ex e mb ia IIC T4 Ga/Gb |
- Intrinsically Safe (Europe)
| ATEX II 1G Ex ia IIC T4 |
- Intrinsically Safe (International)
| IECEx Ex ia IIC T4 |
- Intrinsically Safe (Russia/Kazakhstan)
| EAC Ex ia |
Programming | |
Intrinsically Safe Siemens handheld programmer | Infrared receiver |
- Approvals for handheld programmer
| IS model: ATEX II 1GD Ex ia IIC T4 Ga Ex iaD 20 T135 °C Ta = -20 ... +50 °C CSA/FM Class I, II, and III, Div. 1, Groups A, B, C, D, E, F, G, T6 Ta = +50 °C |
Handheld communicator | HART communicator 375 |
PC | - SIMATIC PDM
- AMS
- SITRANS DTM (for connecting to FDT such as PACTware or Fieldcare)
|
Display (local) | Multi-segment alphanumeric liquid crystal with bar graph (representing level) available in four languages |