The FM 355 and FM 355-2 modules have four separate control channels. The controllers have the following features:
Predefined controller structures for
Fixed setpoint control
Cascade controller
Ratio control
3-component control
Different operating modes
Automatic mode
Manual mode
Safety mode
Follow-up mode
Backup mode
Sampling time (depending on the resolution of the analog inputs and the compensation input):
At 12 bits: 20 ms to 100 ms (FM 355?2 only)
At 14 bits: 100 ms to 500 ms (depending on the number of released analog inputs)
2 control algorithms:
Self-optimizing temperature control algorithm
PID algorithm
Integrated online self-optimization without configuration (FM 355?2 only)
Faster adjustment to the operating point
Convenient controller optimization
Backup mode The controller can continue to control independently in the event of CPU failure or CPU stop. To this end, configurable safety setpoints or safety manipulated variables are set.
Feed forward control The analog inputs can optionally be used for feed forward control in addition to actual value recording.