Standards | | IEC 60947-5-1, EN 60947-5-1, EN ISO 14119 |
Rated insulation voltage Ui | V | 4001) | 400 |
Pollution degree according to IEC 60664-1 | | Class 3 | Class 3 |
Rated impulse withstand voltage Uimp | kV | 6 | 4 |
Rated operational voltage Ue | V | AC 400; over 300 V AC only for equal potential2) | AC 300 |
Conventional thermal current Ith | A | 6 | 10 |
Rated operational current Ie | | 2-pole | 3-pole | 2-pole | |
- With alternating current 50/60 Hz
| | Ie/AC-15 | Ie/AC-15 | Ie/AC-15 |
| A | 6 | 6 | 6 |
| A | 6 | 3 | 6 |
| A | 3 | 1.5 | 3 |
| | Ie/DC-13 | Ie/DC-13 | Ie/DC-13 |
| | 3 | 3 | 3 |
| | 0.55 | 0.55 | 0.55 |
| | 0.27 | 0.27 | 0.27 |
Short-circuit protection3) | | |
- With DIAZED fuse links,
operational class gG
| A | 6 | 10 |
- With miniature circuit breaker, Char. C
| A | 1 | 3 |
Mechanical endurance | | | | |
| | 15 ? 106 operating cycles | 30 ? 106 operating cycles | 30 ? 106 operating cycles |
- With spring rod 3SE5 ...-..R..
| | 10 ? 106 operating cycles | -- | -- |
- With fork lever 3SE5 1..-..T..
| | 1 ? 106 operating cycles | -- | -- |
Electrical endurance | | | | |
- With 3RH.1, 3RT contactors in size S00, S0
| | 10 ? 106 operating cycles | 10 ? 106 operating cycles | 5 ? 106 operating cycles |
- For utilization category AC-15 when switching off Ie/AC-15 at 240 V
| | 100000 operating cycles
| -- | -- |
- With utilization category DC-12/DC-13
| | For direct current depending on the loading of the switch |
Switching frequency with 3RH.1, 3RT contactors in size S00, S0 | | 6000 operating cycles/h | 1800 operating cycles/h |
Switching accuracy for repeated switching, measured at the plunger of the contact block | mm | 0.05 | 0.05 |
| | 1° | 1° |
Rated data in accordance with CSA and UL for USA and Canada |
| V | 300 | 300 |
| A | 6 | 10 |
| | Heavy duty, A 300 / B 300 / Q 300 | A 300 / Q 300 |