Analog input AE1 | See standard controller, Analog input AE1 |
Transmitter supply L+ | |
| 20 to 26 V |
| ? 60 mA, short-circuit proof |
| ? 200 mA, pulsed |
Digital outputs BE1 and BE2 |
| ? 4.5 V or open |
| ? 13 V |
| ? 27 k? |
Digital outputs BA1 and BA2 (with wired OR diodes) | |
| ? 1.5 V |
| +19 to 26 V |
| ? 50 mA |
| ? 80 mA, pulsed |
Analog output Iy (K controller) | |
| 0 to 20 mA or 4 to 20 mA |
| 0 to 20.5 mA or 3.8 to 20.5 mA |
| -1 to +18 V |
- Max. permitted inductive load
| 0.1 H |
Relay output (S controller) | |
| Ag-Ni |
| |
| 250 V AC 250 V DC |
| 8 A 8 A |
| 1250 VA 100 W at 24 V 30 W at 250 V |
Service life | |
Mechanical | 2 . 107 switching operations |
Electrical. 230 V AC, ? loading |
2 . 106 switching operations |
Spark suppressor | 22 nF and 220 ? connected in series with a 420 V varistor wired in parallel |
CPU data | |
| 100 ms |
A/D conversion | |
| Successive approximation with > 120 measurements per input and averaging within 20 or 16.67 ms |
| 18 bit for AE 1 11 bit for further AE and AA |
| ? 0.2 % of measuring span |
| ? 0.2 % of measuring span |
| ? 0.2 % of measuring span |
Display technology |
Digital x indicator | 4-digit, red, 7-segment LED display |
Digital w indicator | 4-digit, green, 7-segment LED display |
| 10 mm |
| Adjustable start and full scale |
| -1999 to +9999 |
| Adjustable (fixed point) |
| 0.1 to 9.9 s, variable |
Analog indicator | Vertical row of 21 LEDs (red) |
| |
| ± 5 % to ± 20 % |
- internal process quantities
| 0 to 100 % |
Basic unit, analog input AE 1 |
Pt100 resistance thermometer |
Line resistance | |
| Line resistance |
| RAb = RL1 + RL4 defined by parameters or automatic compensation via configuration RL1 + RL4 ? 50 ? |
| No compensation necessary if RL1 = RL2 = RL4 ? 50 ? |
| No compensation necessary if RL each ? 100 ? |
Measuring current | 400 ?A |
Configurable measuring range | |
| RtA ? 18.49 ?, tA ? -200 °C |
| RtE ? 390.26 ?, tE ? 850 °C |
Recommended min. span | 10 K |
Characteristic | Temperature linear |
Filter time constant | ? 10 ms |
Input | Non-floating |
Thermocouples TC |
Thermocouples, configurable | Typ |
to DIN IEC 584, Part 1 | Cu-CuNi T |
| Fe-CuNi J |
| NiCr-Ni K |
| NiCr-CuNi E |
| Pt10Rh-Pt S |
| Pt13Rh-Pt R |
| Pt30Rh-Pt6Rh B |
| NiCrSi-NiSi N |
to DIN 43 710 | Cu-CuNi U |
| Fe-CuNi L |
Compensating reference junction | |
| Reference junction terminal required |
| Temperature of external reference junction entered as parameter |
Line resistance | ? 300 ? |
Configurable measuring range | |
| ? -175 mV |
| ? +175 mV |
Recommended min. span | 5 mV |
Configurable characteristic | Linear with voltage or temperature |
Filter time constant | ? 10 ms |
Input current | ? 1 ?A |
Permitted common mode voltage | ? 1 V |
Stat. destruction limit across inputs | ± 35 V |
mV source | |
Configurable measuring range | |
| ? -175 mV |
| ? +175 mV |
Recommended min. span | 5 mV |
Line resistance | ? 1 k? |
Characteristic | Voltage linear |
Input current | ? 1 ?A |
Permitted common mode voltage | ? 1 V |
Stat. destruction limit across inputs | ± 35 V |
Resistance based sensor R | |
| Measuring range |
Configurable measuring range | | |
Measuring range limits incl. line resistance | Rtot ? 600 ?
| Rtot ? 2.8 k?
|
Recommended min. span | 30 ? | 70 ? |
Input current | 400 ?A | 140 ?A |
Linearity error | ± 60 m? | ± 0.2 ? |
Test voltage | 500 V AC |
Input | Non-floating |
mA source with additional measuring range connector 6DR2805-8J (with impedance already included in Smart instruments) |
Measuring range | |
| 0/4 mA ? 0/20 mV |
| 20 mA ? to 100 mV |
Transformation error | 0,3 % |
Input resistance | 50 ? |
Smart input resistance | 250 ? |
Permitted common mode voltage | ? 1 V |
Stat. destruction limit across inputs | ± 40 mA |
10 V voltage source with additional measuring range connector 6DR2805-8J |
Measuring range, can be compensated | |
| 0/2 V ? to 0/20 mV |
| 10 V ? to 100 mV |
Transformation error | 0.2 % |
Input resistance | 90 k? |
Permitted common mode voltage | ? 1 V |
Stat. destruction limit across inputs | ± 35 V |