High availability of the 24 V DC supply thanks to redundant configuration
Decoupling of two power supplies of the same type in parallel operation via diodes
24 V DC power supply is maintained in the event of a power failure
Compact redundancy modules for power supply units up to 40 A
Diagnostic signal via LED and signaling contacts
Adjustable switching threshold for LED and signaling contacts
Buffer module
SITOP buffer module
Buffering the load current during brief power interruptions
Maintenance-free capacitors with short charging times as energy storage units
Wiring parallel to the output of the power supply
Parallel switching of several buffer modules possible
A supply voltage > 20.5 V is signaled by an LED on the device.
Buffer time up to: 200爉s at 40燗, 400爉s at 20燗, 800爉s at 10燗, 1.6爏 at 5燗 load current
Selectivity modules
SITOP selectivity modules
Distribution of the load current over up to 4燾urrent circuits with individually adjustable maximum current
Monitoring of individual partial currents
Reliable tripping regardless of cable lengths and cross-sections
Selective cutoff of current circuits at overload or short-circuit
Simple commissioning thanks to manual switch on/off of outputs
Sequential connection delay of feeders reduces total inrush current
Signaling via LEDs (channel-by-channel) and remote diagnostics via common signaling contact or single-channel signaling
Evaluation of the status of 4 current circuits of selectivity modules with single-channel signaling via SIMATIC S7 function blocks. More information as well as function blocks are available for download at: http://support.automation.siemens.com/WW/view/en/61450284
Remote reset possible from a central location
Sealable transparent cover over adjusters for currents and times for protection against maladjustment