3NE1437-2 Цена на сайте указана розничная в ЕВРО без учета НДС. Для уточнения цены и размера предоставляемой скидки - звоните или присылайте заявки
Заказной номер Вес PG Описание продукта Цена 3NE1437-2 1.13 016 ПЛАВКАЯ ВСТАВКА SITOR КАТЕГОРИЯ GR, DIN 43620 710A , AC 400 V ,(ТИПОРАЗМЕР 3) 207.91 ?
Recommended line-side power components Selection and ordering data The table below lists recommended ratings for input-end switching and fuse protection elements for compliance with IEC standards.
Notes for use in compliance with IEC standards:
3NA3 or 3NE1 fuses are recommended for European countries.
Notes for use in compliance with UL regulations:
UL-approved fuses must be used in North America.
Examples of fuses:Class J and class L fuses, supplied by Cooper Bussmann Additional information about the listed fuses can be found in Catalogs LV 10, IC 10 and IC 10 AO.
Rated power 1)
SINAMICS G120 PM330 Power Modules
Main contactor acc. to IEC
Switch disconnector acc. to IEC
Cable protection fuse incl. semiconductor protection 2)
IEC-compliant
Cable protection fuse acc. to IEC
Cable protection fuse
acc. to UL/cUL, Class J/L
400 V
460 V
Type
Rated current
Minimum short-circuit current
Rated current
Rated current
Minimum short-circuit current
Rated current
kW
hp
6SL3310-...
Frame size
Type
A
A
Type
A
Article No.
A
A
Article No.
A
Reference No. 3)
380 ... 480 V 3 AC
160
200
1PE33-0AA0
GX
3RT1456 (2 units)
400
4400
3KL5730
450
3NE1333-2
400
9500
3NA3260
400
DFJ-400 Class J
200
250
1PE33-7AA0
GX
3RT1456 (2 units)
400
5200
3KL5730
500
3NE1334-2
500
14000
3NA3365
500
DFJ-500 Class J
250
300
1PE34-6AA0
GX
3RT1456 (3 units)
630
6300
3KL6130
560
3NE1435-2
630
20000
3NA3372
600
DFJ-600 Class J
315
400
1PE35-8AA0
HX
3RT1456 (3 units)
630
9000
3KL6130
710
3NE1437-2
650
KTU650 Class L
355
450
1PE36-6AA0
HX
3RT1466 (3 units)
800
10000
3KL6230
800
3NE1438-2
800
30000
3NA3475
700
KTU700 Class L
400
500
1PE37-4AA0
HX
3RT1466 (3 units)
800
12000
3KL6230
850
3NE1448-2
800
KTU800 Class L
1) Rated power based on the rated output current I rated .
2) Suitable for 3KL switch disconnector.
3) Recommendation: Class J or class L fuse supplied by Cooper Bussmann.
Note:
Important! Note the minimum short-circuit current required to trip the protection devices. If the minimum short-circuit current is not reached, the activation time of the fuses is increased, which can lead to damage.