Order No.
|
6EP1 332-4BA00
|
Product
|
S7-1500 PM1507
|
Power supply, type
|
24 V/3 A
|
Input
|
|
Input
|
1-phase AC
|
Rated voltage Uin rated min.
|
|
Supply voltage
|
|
- 1 for AC minimum rated value
|
|
- 2 for AC minimum rated value
|
|
Rated voltage Uin rated max.
|
|
Supply voltage
|
|
- 1 for AC maximum rated value
|
|
- 2 for AC maximum rated value
|
|
|
120 V
|
|
230 V
|
|
…
|
|
Automatic range selection
|
Voltage range
|
…
|
Input voltage
|
|
|
85 … 132 V
|
|
170 … 264 V
|
|
…
|
Overvoltage strength
|
2.3 x Uin rated, 1.3 ms
|
Mains buffering at lout rated, min.
|
20 ms
|
Mains buffering
|
at Uin = 93/187 V
|
Rated line frequency
|
|
|
50 Hz
|
|
60 Hz
|
Line frequency range
|
45 … 65 Hz
|
Input current
|
|
- at rated value of input voltage 120 V rated value
|
1.4 A
|
- at rated value of input voltage 230 V rated value
|
0.8 A
|
- at rated value of input voltage 400 V rated value
|
|
- at rated value of input voltage 500 V rated value
|
|
- for DC at rated value of input voltage 600 V rated value
|
|
Switch-on current limitation (+ 25 °C), max.
|
23 A
|
I²t, max.
|
1.3 A²·s
|
Built-in input fuse
|
T 3.15 A/250 V (not accessible)
|
Protection in the supply feeder (IEC 898)
|
Recommended miniature circuit breaker: 10 A, characteristic B or 6 A, characteristic C
|
Output
|
|
Output
|
Controlled, isolated DC voltage
|
Rated voltage Uout rated DC
|
24 V
|
Total tolerance, static ±
|
1 %
|
Static mains compensation, approx.
|
0.1 %
|
Static load compensation, approx.
|
0.1 %
|
Residual ripple, peak-peak, max.
|
50 mV
|
Residual ripple, peak-peak, typ.
|
|
Spikes peak-peak, max. (bandwidth approx. 20 MHz)
|
150 mV
|
Spikes peak-peak, typ. (bandwidth approx. 20 MHz)
|
|
Adjustment range
|
…
|
Product function: output voltage is adjustable
|
No
|
Setting the output voltage
|
|
Note
|
|
Status display
|
LED green for 24 V O.K.; LED red for fault; LED yellow for stand-by
|
Signaling
|
|
On/Off behavior
|
No overshoot of Uout (soft start)
|
Startup delay, max.
|
1.5 s
|
Note
|
|
Voltage rise, typ.
|
10 ms
|
Maximum voltage rise time of the output voltage
|
|
Rated current Iout rated
|
3 A
|
Current range
|
0 … 3 A
|
Note
|
|
typical active power output
|
72 W
|
short-term overload current in the event of a short circuit during startup, typical
|
12 A
|
Duration of the overload capability overcurrent in the event of a short circuit during startup
|
70 ms
|
constant overload current in the event of a short circuit during startup, typical
|
|
short-term overload current in the event of a short circuit during operation, typical
|
12 A
|
Duration of the overload capability overcurrent in the event of a short circuit during operation
|
70 ms
|
constant overload current in the event of a short circuit during operation, typical
|
|
Parallel switching for enhanced performance
|
Yes
|
Note
|
Parallel connection of 3 A and 8 A possible; devices must be activated simultaneously, at I load max. 75 % per device
|
Number of devices that can be switched in parallel to increase performance, units
|
2
|
Efficiency
|
|
Efficiency at Uout rated, lout rated, approx.
|
87 %
|
Power loss at Uout rated, lout rated, approx.
|
11 W
|
Closed-loop control
|
|
Dynamic mains compensation (Uin rated ±15 %), max.
|
0.1 %
|
Dynamic load compensation (Iout: 50/100/50 %), Uout ± typ.
|
1 %
|
Load-step setting time 50 to 100 %, typ.
|
|
Load-step setting time 100 to 50 %, typ.
|
|
Setting time, maximum
|
5 ms
|
Protection and monitoring
|
|
Output overvoltage protection
|
additional control loop, differentiation (closed-loop control) at < 28.8 V
|
Response value current limitation
|
|
|
3.15 A
|
|
3.6 A
|
Current limitation, typ.
|
3.4 A
|
Property of the output, short-circuit-proof
|
Yes
|
Short-circuit protection
|
electronic shutdown, automatic restart
|
Sustained short-circuit current rms value, typical
|
|
Note
|
|
Overload/short-circuit indicator
|
-
|
Security
|
|
Primary/secondary isolation
|
Yes
|
Electrical isolation
|
Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178 and EN 61131-2
|
Protection class
|
Class I
|
Leakage current
|
|
|
3.5 mA
|
|
0.4 mA
|
CE marking
|
Yes
|
UL/CSA approval
|
|
UL/cUL (CSA) approval
|
Available soon
|
Explosion protection
|
Available soon
|
FM approval
|
|
FM approval
|
|
CB approval
|
Yes
|
Marine approval
|
|
Degree of protection (EN 60529)
|
IP20
|
EMC
|
|
Emitted interference
|
EN 55022 Class B
|
Supply harmonics limitation
|
EN 61000-3-2
|
Noise immunity
|
EN 61000-6-2
|
Operating data
|
|
Ambient temperature
|
|
|
0 … 60 °C
|
|
with natural convection
|
Ambient temperature
|
|
|
-40 … +85 °C
|
|
-40 … +85 °C
|
Humidity class according to EN 60721
|
Climate class 3K3, without condensation
|
Mechanical system
|
|
Connections
|
Screw/spring-type connection technology
|
Connections
|
|
|
L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
|
|
L+, M: 2 screw terminals each for 0.5 ... 2.5 mm²
|
|
|
Width of enclosure
|
50 mm
|
Height of enclosure
|
147 mm
|
Depth of enclosure
|
129 mm
|
Mounting width
|
50 mm
|
Mounting height
|
205 mm
|
Weight, approx.
|
0.45 kg
|
Product property of the enclosure: side-by-side enclosure
|
Yes
|
Type of mounting
|
|
|
No
|
|
No
|
|
No
|
Installation
|
can be mounted onto S7-1500 rail
|
electrical accessories
|
|
mechanical accessories
|
|