Application
|
|
|
Gauge measurement
|
Liquids, gases and vapors
|
|
Mode of operation
|
|
|
Measuring principle
|
Piezoresistive measuring cell (stainless steel diaphragm)
|
|
Measured variable
|
Gauge pressure
|
|
Inputs
|
|
|
Measuring range
|
|
|
|
100 … 600 mbar g (0 … 8.7 psi g)
|
|
Output
|
|
|
Current signal
|
4 ... 20 mA
|
|
|
(UB - 10 V) / 0.02 A
|
|
|
DC 7 ... 33 V (10 ... 30 V for Ex)
|
|
Voltage signal
|
0 ... 10 V DC
|
|
|
≥ 10 kΩ
|
|
|
12 ... 33 V DC
|
|
|
< 7 mA at 10 kΩ
|
|
Characteristic curve
|
Linear rising
|
|
Measuring accuracy
|
|
|
Error in measurement at 25 °C (77 °F), including conformity error, hysteresis and repeatability
|
- Typical: 0.25 % of full-scale value
- Maximum: 0.5 % of full-scale value
|
|
Setting time T99
|
< 0.1 s
|
|
Long-term drift
|
|
- Lower range value and measuring span
|
0.25 % of full-scale value/year
|
|
Influence of ambient temperature
|
|
- Lower range value and measuring span
|
- 0.25 %/10 K of full-scale value
- 0.5 %/10K of full-scale value for a measuring range 100 … 400 mbar
|
- Influence of vibration (per IEC 60068-2-6)
|
0.005 %/g to 500 Hz in all directions
|
- Influence of power supply
|
0.005 %/V
|
|
Conditions of use
|
|
|
Process temperature (see also "Gasket")
|
-30 ... +120 °C (-22 ... +248 °F)
|
|
Ambient temperature
|
-25 ... +85 °C (-13 ... +185 °F)
|
|
Storage temperature
|
-50 ... +100 °C (-58 ... +212 °F)
|
|
Degree of protection (to EN 60529)
|
- IP 65 with connector per EN 175301-803-A
- IP 67 with M12 connector
- IP 67 with cable
- IP 67 with cable quick screw connection
|
|
Electromagnetic compatibility
|
- acc. EN 61326-1/-2/-3
- acc. NAMUR NE21, only for ATEX versions and with a max. measuring deviation ≤ 1 %
|
|
Design
|
|
|
Weight
|
Approx. 0.090 kg (0.198 lb)
|
|
Process connections
|
See dimension drawings
|
|
Electrical connections
|
- Connector per EN 175301-803-A Form A with cable inlet M16x1.5 or ½-14 NPT or Pg 11
- M12 connector
- 2 or 3-wire (0.5 mm2) cable (∅ ± 5.4 mm)
- Cable quick screw connection
|
|
Wetted parts materials
|
|
|
|
Stainless steel, mat.-No. 1.4435
|
|
|
Stainless steel, mat. No. 1.4404 (SST 316 L)
|
|
|
-15 ... +125 °C (+5 ... +257 °F)
-35 ... +100 °C (-31 ... +212 °F
-20 ... +100 °C (-4 ... +212 °F)
-40 ... +145 °C (-40 ... +293 °F), usable for drinking water
|
|
Non-wetted parts materials
|
|
|
|
Stainless steel, mat. No. 1.4404 (SST 316 L)
|
|
|
Plastic
|
|
|
PVC spec.
|
|
Certificates and approvals
|
|
|
Classification according to pressure equipment directive (PED 97/23/EC)
|
For gases of fluid group 1 and liquids of fluid group 1;
meets requirements as per article 3, paragraph 3 (good engineering practice)
|
|
Lloyds Register of Shipping (LR)
|
Applied
|
|
Germanischer Lloyds Register of Shipping (GL)
|
Applied
|
|
American Bureau of Shipping (ABS)
|
Applied
|
|
Bureau Veritas (BV)
|
Applied
|
|
Det Norske Veritas (DNV)
|
Applied
|
|
Drinking water approval (ACS)
|
Applied
|
|
GOST
|
Applied
|
|
Explosion protection
|
|
|
Intrinsic safety "i" (only with current output)
|
Ex II 1/2 G Ex ia IIC T4 Ga/Gb
Ex II 1/2 D Ex ia IIIC T125 °C Da/Db
|
|
EC type-examination certificate
|
SEV 10 ATEX 0146
|
|
Connection to certified intrinsically-safe resistive circuits with maximum values:
|
Ui ≤ 30 V DC; Ii ≤ 100 mA; Pi ≤ 0.75 W
|
|
Effective internal inductance and capacity for versions with plugs per EN 175301-803-A and M12
|