Input
|
|
Measured variable
|
Differential pressure and flow
|
Span (infinitely adjustable)
|
Measuring span
|
Maximum operating pressure
|
|
1,25 ... 250 mbar (0.5 ... 100.4 inH2O)
|
160 bar (2320 psi)
|
|
6,25 ... 1250 mbar (2.5 ... 502 inH2O)
|
Lower measuring limit
|
|
- Measuring cell with silicone oil filling
|
100% of max. span and/or 30 mbar a (0.44 psi a)
|
Upper measuring limit
|
100% of max. span
|
Start of scale
|
Between measuring limits (infinitely adjustable)
|
Output
|
|
Output signal
|
4 ... 20 mA
|
- Lower limit (
infinitely adjustable)
|
3.55 mA, factory preset to 3.8 mA
|
- Upper limit (
infinitely adjustable)
|
23 mA, factory setting 20.5 mA
|
- Ripple
(without HART communication)
|
I pp ≤ 0.5 of max. output current
|
|
0... 100 s in steps of 0.1 s, factory-set to 2 s
|
|
3.55 ... 23 mA
|
|
adjustable within limits:
- Bottom: 3,55 … 3,7 mA
- Top: 21,0 … 23 mA
|
Load
|
|
- Without HART communication
|
R
B ≤ (UH - 10.5 V)/0.023 A in Ω, UH : Power supply in V
|
|
|
|
R
B = 230 ... 1100 Ω
|
|
R
B = 230 ... 500 Ω
|
Characteristic curve
|
Linearly rising, linearly falling, square rooted characteristic rising, bidirectional square rooted characteristic and user-specific
|
Measuring accuracy
|
|
Reference conditions (in accordance with IEC 60770-1)
|
- Rising characteristic curve
- Start of scale 0 bar
- Stainless steel seal diaphragm
- Measuring cell with silicone oil filling
- Room temperature (25 °C (77 °F))
- r: Span ratio
|
- (r = max. span / adjusted span)
|
Total accuracy (Total Performance)
|
|
Linear characteristic
|
|
|
≤ 0,09 %
|
|
≤ 0,11 %
|
Square-rooted characteristic
|
|
|
|
|
≤ 0,09 %
|
|
≤ 0,11 %
|
|
|
|
≤ 0,18 %
|
|
≤ 0,22 %
|
Conformity error at limit setting incl. hysteresis and reproducibility
|
|
Linear characteristic
|
|
|
≤ 0,04 %
|
|
(0,003 . r + 0.01) %
|
Square-rooted characteristic
|
|
|
|
|
≤ 0,04 %
|
|
(0,003 . r + 0.01) %
|
|
|
|
≤ 0,08 %
|
|
(r + 0.02 . 0,06) %
|
Influence of ambient temperature per 28 °C
|
(0,006 . r + 0.01) % /28%
|
Influence of static pressure
|
|
|
≤ 0.005 % per 70 bar
|
|
≤ 0.03 % per 70 bar
|
Step response time T63 without electrical damping
|
≤ 90 ms
|
Long-term stability
|
≤ 0.1 · ) % per 5 years
≤ 0.15 · ) % per 10 years
|
Influence of power supply
|
≤ 0.005 ... 1 V
|
Rated conditions
|
|
Mounting position
|
Any
|
Ambient conditions
|
|
- Ambient temperature
(Note: Observe the temperature class in areas subject to explosion hazard.)
|
|
|
-40 ... +85 °C (-40 ... +185 °F)
|
|
-20 ... +85 °C (-4 ... +185 °F)
|
|
-50 ... +90 °C (-58 ... +194 °F)
|
Climatic class
|
|
|
Relative humidity 0 … 100 % (condensation permissible)
|
Degree of protection (to EN 60529)
|
IP66/IP68 (with corresponding cable gland)
|
Electromagnetic Compatibility
|
|
- Emitted interference and interference immunity
|
Acc. to EN 61326 and NAMUR NE 21
|
Permissible pressures
|
According to 97/23/EC pressure equipment directive
|
Temperature of medium
|
|
- Measuring cell with silicone oil filling
|
-40 ... +125 °C (-40 ... +257 °F)
|
|
(Notes that the process flanges will not admit a flow of medium of temperature > 100 °C.)
|
Design
|
|
Weight (without options)
|
Approx. 3,3 kg (7.3 lb)
|
Material of parts in contact with the medium
|
|
|
Stainless steel, mat. no. 1.4404/316L
|
- Process connection and sealing screw
|
- PN 160: stainless steel, mat.-No. 1.4404
|
|
Standard: Viton (FKM (FPM)) optional: NBR
|
Material of parts not in contact with media
|
|
Electronics housing
|
- Low copper die-cast aluminum AC-AlSi12 (Fe) or AC-AlSi 10 Mg (Fe) to DIN EN 1706
- Lacquer on polyurethane base, optional epoxy-based primer
- Stainless steel serial plate
|
Process connection screws
|
Stainless steel
|
Mounting bracket
|
Steel or stainless steel
|
Measuring cell filling
|
Silicone oil
|
Process connection
|
¼-18 NPT female thread and flange connection with M10 to DIN 19213 or 7/16-20 UNF mounting thread to EN 61518
|
Electrical connection
|
- Screw terminals
- Cable entry via the following screwed glands:
- M20 x 1.5
- ½-14 NPT
- Han 7D/Han 8D connector
- M12 plug
|
Displays and controls
|
|
Keys
|
3 for local programming directly on transmitter
|
Digital display
|
- With or without integrated digital display (optional)
- Cover with or without window (optional)
|
Auxiliary power supply
|
|
Terminal voltage on transmitter
|
- DC 10.5 V ... 45 V
- With intrinsically-safe operation DC 10.5 V ... 30 V
|
Separate power supply
|
|
Certificates and approvals
|
|
Classification according to PED 97/23/EC
|
|
|
For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)
|
Explosion protection
|
|
Explosion protection for Europe (to ATEX)
|
|
|
PTB 09 ATEX 2004 X
|
|
Ex II 1/2 G Ex ia/ib IIC T4
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F)
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW; Ri = 300 Ω
|
- Effective internal inductance:
|
Li = 400µH
|
- Effective inner capacitance:
|
Ci = 6 nF
|
|
BVS 09 ATEX E 027
|
|
Ex II 1/2 G Ex d IIC T4/T6
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F) temperature class T4; -40 ... +60 °C (-40 ... +140 °F) temperature class T6
|
|
To circuits with values: Um = DC 10.5 ... 45 V
|
- Dust explosion protection for zone 20
|
PTB 09 ATEX 2004 X
|
|
Ex II 1 D Ex iaD 20 T 120 °C
|
- Permissible ambient temperature
|
-40 ... +85 °C (-40 ... +185 °F)
|
|
120 °C (248 °F)
|
|
To certified intrinsically-safe circuits with peak values: Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Ω
|
- Effective internal inductance:
|
Li = 400µH
|
- Effective inner capacitance:
|
Ci = 6 nF
|
- Dust explosion protection for zone 21/22
|
BVS 09 ATEX E 027
|
|
Ex II 2 D IP65 T 120 °C
|
|
To circuits with values: UH = 10.5 ... 45 V DC; Pmax = 1.2 W
|
- Type of protection "n" (zone 2)
|
PTB 09 ATEX 2004 X
|
|
Ex II 3 G Ex nA II T4/T6 Ex II 2/3 G Ex ib/nL IIC T4/T6 Ex II 2/3 G Ex ib/ic IIC T4/T6
|
|
Um = 45 V DC
|
|
Ui = 45 V
|
- Effective internal inductance:
|
Li = 400µH
|
- Effective inner capacitance:
|
Ci = 6 nF
|
Explosion protection for USA (to FM)
|
|
Certificate of Compliance
|
No. 3033013
|
- Identification (XP/DIP) or (IS)
|
XP CL I, DIV 1, GP ABCDEFG T4 / T6 DIP CL II, III, DIV1, GP EFG T4/T6 IS CL I, II, III, DIV1, GP ABCDEFG T4
CL I, Zone 0, AEx ia IIC T4 CL I, Zone 1, AEX ib IIC T4
|
- Permissible Ambient Temperature
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
|
|
According to "control drawing": Vmax = 30 V, Imax = 100 mA, Pi = 750 mW, Li = 400µH , Ci = 6 nF
|
|
NI CL I, DIV2, GP ABCD T4/T6 NI CL I, Zone 2, GP IIC T4/T6 S CL II, III, GPFG T4/T6 NI CL I, DIV2, GP ABCD T4/T6, NIFW NI CL I, Zone 2, GP IIC T4/T6, NIFW NI CLII, III, DIV2, GP FG T4/T6, NIFW
|
- Permissible Ambient Temperature
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
|
|
According to "control drawing": Vmax = 45 V, Li = 400µH, Ci = 6 nF,
|
Explosion protection for Canada (to
C
CSA
US
)
|
|
Certificate of Compliance
|
No. 2280963
|
|
CL I, DIV 1, GP ABCD T4 /T6; CL II, DIV 1, GP EFG T4/T6
|
- Permissible Ambient Temperature
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
|
|
According to "control drawing": Vmax = 45 V
|
|
CL I, Ex ia/Ex ib IIC, T4 CL II, III, Ex ia/Ex ib, GP EFG, T4 CL I, AEx ia/AEx ib IIC, T4 CL II, III, AEx ia/ AEx ib, GP EFG, T4
|
- Permissible Ambient Temperature
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F)
|
|
Ui = 30 V, Ii = 100 mA, Pi = 750 mW, Ri = 300 Ω , Li = 400 µH, Ci = 6 nF
|
|
CL I, DIV2, GP ABCD T4/T6 CL II, III, DIV2, GP FG T4/T6 Ex nA IIC T4/T6 AEx nA IIC T4/T6 Ex nL IIC T4/T6 AEx nL IIC T4/T6
|
- Permissible Ambient Temperature
|
Ta = T4: -40 ... +85 °C (-40 ... +185 °F) Ta = T6: -40 ... +60 °C (-40 ... +140 °F)
|
|
According to "control drawing": Vmax = 45 V
|
|
According to "control drawing": Ui = 45 V, Ii = 100 mA, Li = 400 µH, Ci = 6 nF
|