Заказной номерВесPGОписание продуктаЦена
7MF4634-.....-....4.5805ДАТЧИК ДАВЛЕНИЯ ДЛЯ ИЗМЕРЕНИЯ УРОВНЯ SITRANS P DS III PA1674.8

For filling level

SITRANS P DS III for level

HART

PROFIBUS PA or Foundation Fieldbus

Input

Measured variable

Level

Spans (infinitely adjustable) or nominal measuring range and max. permissible operating pressure

Span (min. ... max.)

Maximum operating pressure

Nominal measuring range

Maximum operating pressure

25 ... 250 mbar
(10 ... 100 inH2O)

See "Mounting flange"

250 mbar
(100 inH2O)

See "Mounting flange"

25 ... 600 mbar
(10 ... 240 inH2O)

See "Mounting flange"

600 mbar
(600 inH2O)

See "Mounting flange"

53 ... 1600 mbar
(21 ... 642 inH2O)

See "Mounting flange"

1600 mbar
(642 inH2O)

See "Mounting flange"

160 ... 5000 mbar
(64 ... 2000 inH2O)

See "Mounting flange"

5000 mbar
(2000 inH2O)

See "Mounting flange"

Lower measuring limit

  • Measuring cell with silicone oil filling

-100 % of max. span or 30 mbar a (0.44 psi a), depending on mounting flange

Upper measuring limit

100% of max. span

100 % of the max. nominal measuring range

Output

Output signal

4 ... 20 mA

Digital PROFIBUS PA and FOUNDATION Fieldbus signal

  • Lower limit (infinitely adjustable)

3.55 mA, factory preset to 3.84 mA

-

  • Upper limit (infinitely adjustable)

23 mA, factory preset to 20.5 mA or optionally set to 22.0 mA

-

Load

  • Without HART

R B (UH - 10.5 V)/0.023 A in ,
UH: Power supply in V

-

  • With HART

R B = 230 ... 500 (SIMATIC PDM) or
RB = 230 ... 1100 (HART Communicator)

-

Physical bus

-

IEC 61158-2

Protection against polarity reversal

Protected against short-circuit and polarity reversal. Each connection against the other with max. supply voltage.

Measuring accuracy

According to IEC 60770-1

Reference conditions
(All error data refer always refer to the set span)

Increasing characteristic, start-of-scale value 0 bar, stainless steel seal diaphragm, silicone oil filling, room temperature 25 °C (77 °F), r: Span ratio
(r = max. span / set span)

Error in measurement at limit setting incl. hysteresis and reproducibility

  • Linear characteristic

 0,15 %

  • r   10

 0,15 %

  • 10 < r 30

 0,3 %

  • 30 < r   100

 (0.0075 · r + 0.075) %

Long-term stability (temperature change ± 30 °C (± 54 °F))

 (0.25 · r)% every 5 years
static pressure max. 70 bar g (1015 psi g)

 0.25 % every 5 years
static pressure max. 70 bar g (1015 psi g)

Influence of ambient temperature

  • at -10 ... +60 °C (14 ... 140 °F)

  • 250 mbar- (100 inH2O)-measuring cell

 (0.5 · r + 0.2) %1)4)

 0,7 %

  • 600 mbar- (240 inH2O)-measuring cell

 (0.3 · r + 0.2) %2)4)

 0,5 %

  • 1600 and 5000 mbar- (642 and 2000 inH2O)-measuring cell

 (0.25 · r + 0.2) %3)4)

 0,45 %

  • at -40 ... -10 °C and +60 ... +85 °C
    (-40 ... +14 °F and 140 ... 185 °F)

  • 250 mbar- (100 inH2O)-measuring cell

 (0.25 · r + 0.15) %/10 K
doubled values at 10 < r 30 

 0.4 %/10 K

  • 600 mbar- (240 inH2O)-measuring cell

 (0.15 · r + 0.15) %/10 K
doubled values at 10 < r 30

 0.3 %/10 K

  • 1600 and 5000 mbar- (642 and 2000 inH2O)-measuring cell

 (0.12 · r + 0.15) %/10 K
double values at 10 < r   30

 0.27 %/10 K

Influence of static pressure

  • on the zero point

  • 250 mbar- (100 inH2O)-measuring cell

 (0.3 · r) % per nominal pressure

 0.3 % per nominal pressure

  • 600 mbar- (240 inH2O)-measuring cell

 (0.15 · r) % per nominal pressure

 0.15 % per nominal pressure

  • 1600 and 5000 mbar- (642 and 2000 inH2O)-measuring cell

 (0.1 · r) % per nominal pressure

 0.1 % per nominal pressure

  • on the span

 (0.1 · r) % per nominal pressure

 0.1 % per nominal pressure

Measured Value Resolution

-

3 · 10-5 of nominal measuring range

Rated conditions

Degree of protection to IEC 60529

IP65, optional IP68

Temperature of medium

Note: Always take into account assignment of max. permissible operating temperature to max. permissible operating pressure of the respective flange connection!

  • Measuring cell with silicone oil filling

-40 ... +100 °C (-40 ... +212 °F)

  • High-pressure side

pabs 1 bar: -40 ... +175 °C (-40 ... +347 °F)

pabs < 1 bar: -40 ... +80 °C (-40 ... +176 °F)

  • Low-pressure side

-40 ... +100 °C (-40 ... +212 °F)

-20 ... +60 °C (-4 ... +140 °F) in conjunction with dust explosion protection

Ambient conditions

  • Ambient temperature

  • Display readable

-30 ... +85 °C (-22 ... +185 °F)

  • Storage temperature

-50 ... +85 °C (-58 ... +185 °F)

  • Climatic class

  • Condensation

Relative humidity 0 ... 100 %
Condensation permissible, suitable for use in the tropics

  • Electromagnetic Compatibility

  • Emitted interference and interference immunity

Acc. to EN 61326 and NAMUR NE 21

Design

Weight (without options)

To EN (pressure transmitter with mounting flange, without tube)

 11 ... 13 kg (  24.2 ... 28.7 lb)

To ASME (pressure transmitter with mounting flange, without tube)

 11 ... 18 kg (  24.2 ... 39.7 lb)

Enclosure material

Low-copper die-cast aluminum, GD-AlSi 12 or stainless steel precision casting, mat. no. 1.4408

Wetted parts materials

High-pressure side:

  • Seal diaphragm of mounting flange

Stainless steel, mat. no. 1.4404/316L, Monel, mat. no. 2.4360, Hastelloy B2, mat. no. 2.4617, Hastelloy C276, mat. no. 2.4819, Hastelloy C4, mat. no. 2.4610, tantalum, PTFE, ECTFE

Measuring cell filling

Silicone oil

Process connection

  • High-pressure side

Flange to EN and ASME

  • Low-pressure side

Female thread -18 NPT and flange connection with mounting thread M10 to DIN 19213 or7/16-20 UNF to IEC 61518

Power supply U H

Supplied through bus

Terminal voltage on transmitter

10.5 ... 45 V DC
10.5 ... 30 V DC in intrinsically-safe mode

-

Separate 24 V power supply necessary

-

No

Bus voltage

  • Not Ex

-

9 ... 32 V

  • With intrinsically-safe operation

-

9 ... 24 V

Current consumption

  • Basic current (max.)

-

12.5 mA

  • Start-up current basic current

-

Yes

  • Max. current in event of fault

-

15.5 mA

Fault disconnection electronics (FDE) available

-

Yes

Certificates and approvals

Classification according to PED 97/23/EC

For gases of fluid group 1 and liquids of fluid group 1; complies with requirements of article 3, paragraph 3 (sound engineering practice)

Explosion protection

  • Intrinsic safety "i"

PTB 99 ATEX 2122

  • Marking

Ex II 1/2 G EEx ia/ib IIB/IIC T6

  • Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +70 °C (-40 ... +158 °F) temperature class T5;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6

  • Connection

To certified intrinsically-safe circuits with peak values:
Ui = 30 V,Ii = 100 mA,
Pi = 750 mW;Ri = 300 

FISCO supply unit:
Uo = 17.5 V,Io = 380 mA,Po = 5.32 W

Linear barrier:
Uo = 24 V,Io = 250 mA,Po = 1.2 W

  • Effective internal inductance/capacitance

L i = 0.4 mH,Ci = 6 nF

L i = 7 H,Ci = 1.1 nF

  • Explosion-proof "d"

PTB 99 ATEX 1160

  • Marking

Ex II 1/2 G EEx d IIC T4/T6

  • Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F) temperature class T4;
-40 ... +60 °C (-40 ... +140 °F) temperature class T6

  • Connection

To circuits with values:UH = 10.5 ... 45 V DC

To circuits with values:UH = 9 ... 32 V DC

  • Dust explosion protection for zone 20

PTB 01 ATEX 2055

  • Marking

Ex II 1 D IP65 T 120 °C
Ex II 1/2 D IP65 T 120 °C

  • Permissible ambient temperature

-40 ... +85 °C (-40 ... +185 °F)

  • Max. surface temperature

120 °C (248 °F)

  • Connection

To certified intrinsically-safe circuits with peak values:
Ui = 30 V,Ii = 100 mA,
Pi = 750 mW,Ri = 300

FISCO supply unit:
Uo = 17.5 V,Io = 380 mA,Po = 5.32 W

Linear barrier:
Uo = 24 V,Io = 250 mA,Po = 1.2 W

  • Effective internal inductance/capacitance

L i = 0.4 mH,Ci = 6 nF

L i = 7 H,Ci = 1.1 nF

  • Dust explosion protection for zone 21/22

PTB 01 ATEX 2055

  • Marking

Ex II 2 D IP65 T 120 °C

  • Connection

To circuits with values:UH = 10.5 ... 45 V DC;Pmax = 1.2 W

To circuits with values:UH = 9 ... 32 V DC;Pmax = 1.2 W

  • Type of protection "n" (zone 2)

TUV 01 ATEX 1696 X

TUV 01 ATEX 1696 X

  • Marking

Ex II 3 G EEx nA L IIC T4/T5/T6

Ex II 3 G EEx nA L IIC T4/T5/T6

  • Explosion protection acc. to FM

Certificate of Compliance 3008490

  • Identification (XP/DIP) or (IS); (NI)

CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; CL I, ZN 0/1 AEx ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III

  • Explosion protection to CSA

Certificate of Compliance 1153651

  • Identification (XP/DIP) or (IS)

CL I, DIV 1, GP ABCD T4...T6; CL II, DIV 1, GP EFG; CL III; Ex ia IIC T4...T6; CL I, DIV 2, GP ABCD T4...T6; CL II, DIV 2, GP FG; CL III


1) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.4 · r + 0.16) % / 28 °C (50 °F).

2) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.24 · r + 0.16) % / 28 °C (50 °F).

3) Conversion of temperature error per 28 °C. Valid for temperature range -3 ... +53 °C < (0.2 · r + 0.16) % / 28 °C (50 °F).

4) 0.32 in place of 0.16 at 10 < r < 30

HART communication

HART

230 ... 1100 

Protocol

HART Version 5.x

Software for computer

SIMATIC PDM


PROFIBUS PA communication

Simultaneous communication with master class 2 (max.)

4

The address can be set using

Configuration tool or local operation (standard setting address 126)

Cyclic data usage

  • Output byte

5 (one measured value) or
10 (two measured values)

  • Input byte

0, 1, or 2 (register operating mode and reset function for metering)

Internal preprocessing

Device profile

PROFIBUS PA Profile for Process Control Devices Version 3.0, Class B

Function blocks

2

  • Analog input

  • Adaptation to customer-specific process variables

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 & 100 s

  • Simulation function

Input /Output

  • Failure mode

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Register (totalizer)

Can be reset, preset, optional direction of counting, simulation function of register output

  • Failure mode

parameterizable (summation with last good value, continuous summation, summation with incorrect value)

  • Limit monitoring

One upper and lower warning limit and one alarm limit respectively

  • Physical block

1

Transducer blocks

2

  • Pressure transducer block

  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Specification of a container characteristic with

Max. 30 nodes

  • Square-rooted characteristic for flow measurement

Yes

  • Gradual volume suppression and implementation point of square-root extraction

Parameterizable

  • Simulation function for measured pressure value and sensor temperature

Constant value or over parameterizable ramp function


FOUNDATION Fieldbus communication

Function blocks

3 function blocks analog input, 1 function block PID

  • Analog input

  • Adaptation to customer-specific process variables

Yes, linearly rising or falling characteristic

  • Electrical damping adjustable

0 & 100 s

  • Simulation function

Output/input (can be locked within the device with a bridge)

  • Failure mode

parameterizable (last good value, substitute value, incorrect value)

  • Limit monitoring

Yes, one upper and lower warning limit and one alarm limit respectively

  • Square-rooted characteristic for flow measurement

Yes

  • PID

Standard FOUNDATION Fieldbus function block

  • Physical block

1 resource block

Transducer blocks

1 transducer block Pressure with calibration, 1 transducer block LCD

  • Pressure transducer block

  • Can be calibrated by applying two pressures

Yes

  • Monitoring of sensor limits

Yes

  • Simulation function: Measured pressure value, sensor temperature and electronics temperature

Constant value or over parameterizable ramp function


Mounting flange

Nominal diameter

Nominal pressure

  • Acc. to EN 1092-1

  • DN 80

PN 40

  • DN100

PN16, PN40

  • To ASME B16.5

  • 3 inch

Class 150, class 300

  • 4 inch

Class 150, class 300
























































Каталог оборудования 2012
Каталог продуктов Siemens Industry Приводная техника Техника автоматизации Системы автоматизации Системы визуализации SIMATIC HMI Системы идентификации Промышленные коммуникации SIMATIC NET Промышленные аппараты управления SIRIUS Промышленные информационные технологии Управление на базе РС Системы управления процессом Датчики Контрольно-измерительные приборы Pressure gauge Transmitter for gauge, absolute and differ. pressure, flow and level Measurement transducer for basic requirements Transmitter with WirelessHART communication Transmitters for food, pharmaceuticals and biotechnology Transmitter for gauge pressure for the paper industry Transmitter for general requirements SITRANS P DS III, technical description For gauge pressure For gauge and absolute pressure, with flush-mounted diaphragm For absolute pressure (from the gauge pressure series) For absolute pressure (from the differential pressure series) For differential pressure and flow For filling level Accessories Transmitter for high-end requirements Remote seals for transmitters and pressure gauges Fittings Датчики давления Приборы измерения температуры SITRANS T Расходомеры Уровнемеры Расходомеры и счетчики Позиционеры Устройство для защиты и пуска двигателей SIMOCODE-DP Блок питания/искробезопасной развязки датчиков SITRANS I Источники питания и разделители Сигнализаторы сбоев в промышленном процессе Аппаратные ПИД-регуляторы SIPART Встраиваемые самописцы и индикаторы Коммуникации и программное обеспечение Анализаторы процесса Технологии взвешивания Датчики зрения Блоки питания Продукты для специальных требований Автоматизация зданий Низковольтная коммутационная техника Технология безопасности Системные решения и продукты для отраслей Сервис ... и все, что Вам еще необходимо