Siemens
СРЕДСТВА ПРОМЫШЛЕННОЙ АВТОМАТИЗАЦИИ
официальный партнер Сименс
Каталог СА01 2012
архивный
(4872) 700-366
skenergo@mail.ru

6ES7960-1AA04-5BA0


Внимание! Указаны цены архивного каталога СА01. Для уточнения актуальной цены перейдите по ссылке заказного номера товара или перейдите в каталог СА01 2016

Заказной номерВесPGОписание продуктаЦена
6ES7960-1AA04-5BA00.04240SIMATIC S7-400H. ОПТОВОЛОКОННЫЙ КАБЕЛЬ ДЛИНОЙ 2M ДЛЯ СУБМОДУЛЯ СИНХРОНИЗАЦИИ93.7

SIPLUS sync module for coupling the CPU 41xH
  • For linking the two CPUs 414-4H/417-4H in the subunits of the S7-400H
  • Can be plugged direct into the CPU

Note:

SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.

SIPLUS sync module (up to 10 m)

Order number

6AG1 960-1AA04-4XA0

Order number based on

6ES7 960-1AA04-0XA0

Ambient temperature range

0 ... +60 °C

Conformal coating

Coating of the printed circuit boards and the electronic components

Technical data

The technical data of the standard product applies except for the environmental conditions.

Ambient conditions

Relative humidity

5 ... 100 %
Condensation permissible

Biologically active substances

Conformity with EN 60721 3 3, Class 3B2 mold and fungal spores (except fauna)

Chemically active substances

Conformity with EN 60721 3 3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX1)2)

Mechanically active substances

Conformity with EN 60721 3 3, Class 3S4 including conductive sand, dust2)

Air pressure (depending on the highest positive temperature range specified)

1080 ... 795 hPa (-1000 ... +2000 m)
see ambient temperature range

795 ... 658 hPa (+2000 ... +3500 m)
derating 10 K

658 ... 540 hPa (+3500 ... +5000 m)
derating 20 K


1) ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm

2) The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!

Technical documentation on SIPLUS is available under:
http://www.siemens.com/siplus-extreme
























































  © ООО "СК ЭНЕРГО" 2007-2022
  (4872) 700-366
Яндекс.Метрика