6ES7912-0AA00-0AA0
Внимание! Указаны цены архивного каталога СА01. Для уточнения актуальной цены перейдите по ссылке заказного номера товара или перейдите в каталог СА01 2016
Заказной номер | Вес | PG | Описание продукта | Цена |
6ES7912-0AA00-0AA0 | 0.006 | 230 | SIMATIC S7. ПЛАСТИКОВЫЕ МЕТКИ МАРКИРОКИ НОМЕРОВ МОДУЛЕЙ В МОНТАЖНЫХ СТОЙКАХ S7-300/ S7-400/ ET 200M/ C7 | 6.49 |
CPU for SIMATIC S7-400H and S7-400F/FH
- Usable in high-availability systems such as the S7-400H
- Usable with F runtime license as F-capable CPU in S7-400F/FH safety-related systems
- With integral PROFIBUS DP master interface
- Features 2 slots for sync modules
Note:
SIPLUS extreme products are based on Siemens Industry standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
SIPLUS CPU 414-4H |
|
Order number |
6AG1 414-4HM14-4AB0 |
Order No. based on |
6ES7 414-4HM14-0AB0 |
Ambient temperature range |
0 ... +60 °C |
Conformal coating |
Coating of the printed circuit boards and the electronic components |
Technical data |
The technical data of the standard product applies except for the environmental conditions. |
Ambient conditions |
|
Relative humidity |
5 ... 100 % |
Biologically active substances |
Conformity with EN 60721 3 3, Class 3B2 mold and fungal spores (except fauna) |
Chemically active substances |
Conformity with EN 60721 3 3, Class 3C4 incl. salt mist and ISA–S71.04 severity level G1; G2; G3; GX1)2) |
Mechanically active substances |
Conformity with EN 60721 3 3, Class 3S4 including conductive sand, dust2) |
Air pressure (depending on the highest positive temperature range specified) |
1080 ... 795 hPa (-1000 ... +2000 m) 795 ... 658 hPa (+2000 ... +3500 m) 658 ... 540 hPa (+3500 ... +5000 m) |
1) ISA-S71.04 severity level GX: Long-term load: SO2 < 4.8 ppm; H2S < 9.9 ppm; Cl < 0.2 ppm; HCl < 0.66 ppm; HF < 0.12 ppm; NH < 49 ppm; O3 < 0.1 ppm; NOX < 5.2 ppm
Limit value (max. 30 min/d): SO2 < 17.8 ppm; H2S < 49.7 ppm; Cl < 1.0 ppm; HCl < 3.3 ppm; HF < 2.4 ppm; NH < 247 ppm; O3 < 1.0 ppm; NOX < 10.4 ppm
2) The supplied plug covers must remain in place over the unused interface when operated in atmospheres containing corrosive gases!
The technical documentation on SIPLUS can be found here:
http://www.siemens.de/siplus-extreme